INNOV@ ECFAN DHR -AGU-0912-E • 35 •
tab. 11 DX unit (1 compressor) - water condensed - DHWDR - DHWUR
MODELS
DHWDR
DHWUR
0201 0251 0281 0311 0401
Power supply
V/Ph/Hz
400V / 3Ph + N + PE / 50Hz
Air flow
m
3
/h
6800 7280 12950
WATER TEMPERATURE 40C / 45C (30% e.g.)
Cooling capacity
kW
21.71 22.74 27.13 30.17 40.95
Power consumption
kW
5.84 6.16 7.40 8.66 11.55
Waterflow
[l/h]
5380 5634 6653 7571 9957
Pressure drop
[kPa]
16.9 19.5 16.7 21.1 34.5
COMPRESSOR
Type
-
Scroll
Power supply
V/Ph/Hz
400V / 3Ph / 50Hz
Nominal current
A
8.91 9.41 11.48 13.46 16.42
FLA
A
17 20 29
LRA
A
86 98 130 135
Oil charge
l
3.25 4.25 3.30
FINNED EVAPORATOR COIL
Front surface
m
2
0.7 0.9 1.3
Geometry
-
25 x 22 25 x 22 25 x 22 25 x 22 25 x 22
Rows
Nr.
5 4
Type of fins
Type
Hydrophilic
Fin pitch
mm
2.1
SHR
-
0.88 0.87 0.84 0.79 0.86
FAN SECTION
Type of fans
Tipo
Radial - EC
Fans
Nr.
1 2
Current consumption
A
1.61 2.01 3.07
Power consumption
W
1007 1252 1912
AESP
Pa
30
AESP (max. fan speed)
Pa
367.5 298.4 382.2
FILTER SECTION
Filter efficiency
-
G4
Overall surface
m
2
1.44 2.92
Fire resistance class
-
1
ELECTRICAL HEATERS
Total heating capacity
kW
6.4 9.6
Heaters
Nr.
4 6
Material
-
Aluminium
HOT GAS REHEATING COIL
Heating capacity
kW
16.50 16.70 17.30 - 37.20
Front surface
m
2
0.7 0.9 1.3
HOT WATER REHEATING COIL
Heating capacity (water 45/40C)
kW
14.50 14.70 14.90 - 29.60
Front surface
m
2
0.7 0.9 1.3
Water flow
m
3
/h
2494 2528 2563 - 5091
Water side pressure drop
kPa
13.00 - 42.00
Valve pressure drop
kPa
14.72 15.13 15.55 - 10.13
HUMIDIFIER
Capacity
kg/h
9.00 8.83 8.64 8.39 8.78
Power consumption
kW
2.25 6.00
DIMENSIONS
Height x Lenght x Depth
mm
1998 x 1010 x 795 1998 x 1270 x 795 1998x1760x796
Unit weight
kg
375 385 490 505 595