EasyManua.ls Logo

Lennox INNOV DM R Series - Page 69

Lennox INNOV DM R Series
106 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
INNOV@ ECFAN DHR -AGU-0912-E 37
MODELS
DHWDR
DHWUR
0532 0592 0602 0692 0762
Power supply V/Ph/Hz
400V / 3Ph + N + PE / 50Hz
Air flow
m
3
/h
14150 19415
WATER TEMPERATURE 40C / 45C (30% e.g.)
Cooling capacity
kW
52.32 58.06 62.10 69.85 77.02
Power consumption
kW
14.78 17.28 17.34 20.18 22.98
Waterflow
[l/h]
13160 14452 14986 17118 18978
Pressure drop
[kPa]
16.4 19.4 20.7 26.3 31.6
COMPRESSOR
Type
-
Scroll
Nominal current
V/Ph/Hz
400V / 3Ph / 50Hz
Nominal current
A
11.48 13.43 13.45 16.37 16.35
FLA
A
20 29 32
LRA
A
130 135
Oil charge
l
3.25 3.30 3.25
FINNED EVAPORATOR COIL
Front surface
m
2
1.5 1.9
Geometry
-
25 x 22
Rows
Nr.
4
Type of fins
Type
Hydrophilic
Fin pitch
mm
2.1
SHR
-
0.79 0.76 0.85 0.80 0.76
FAN SECTION
Type of fans
Tipo
Radial - EC
Fans
Nr.
2 3
Current consumption
A
3.98 4.41
Power consumption
W
2718 3074
AESP
Pa
30
AESP (max. fan speed)
Pa
274.2 363.0
FILTER SECTION
Filter efficiency
-
G4
Overall surface
m
2
4.49
Fire resistance class
-
1
ELECTRICAL HEATERS
Total heating capacity
kW
9.6 12.8
Heaters
Nr.
6 8
Material
-
Aluminium
HOT GAS REHEATING COIL
Heating capacity
kW
38.60 - 51.30 52.70 53.90
Front surface
m
2
1.5 1.9
HOT WATER REHEATING COIL
Heating capacity (water 45/40C)
kW
31.30 - 44.30 46.00 47.60
Front surface
m
2
1.5 1.9
Water flow
m
3
/h
5.384 - 7.620 7.912 8.187
Water side pressure drop
kPa
45.00 - 34.00 35.00 39.00
Valve pressure drop
kPa
29.00 - 27.00
HUMIDIFIER
Capacity
kg/h
8
Power consumption
kW
6
DIMENSIONS
Height x Lenght x Depth
mm
1998 x 2020 x 795 1998 x 2510 x 795
Unit weight
kg
730 745 940 958 979

Related product manuals