EasyManuals Logo

Lennox LGT Series User Manual

Lennox LGT Series
61 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #49 background imageLoading...
Page #49 background image
Page 49
VIII-Direct Drive Supply Air Inverter
If a test and balance contractor has not commissioned the

A-Set Blower Speed
1 - 

TABLE 16

Blower Speed 


Cooling Medium
Cooling Low
Ventilation
2 - Use the following menu to enter the blower design



the Unit Controller manual provided with unit.

3 - 

RPM will be displayed.
Note - When units are not equipped with heat, the
Blower Heat speed will not be displayed. Blower
Cooling High will be the rst blower speed to appear.
4 - Measure the static pressure as shown in the Blower
      
       


 Enter the RPM and repeat the previous step until

6 - Press SAVE followed by MAIN MENU.
Note - Once the CFM settings are saved, the Unit
Controller will set all other blower CFM.
B-Set Damper Minimum Position
To maintain required minimum ventilation air volumes
         
damper positions must be set. The Unit Controller will
open the dampers to “Min OCP Blwr Low” when blower

         


Set Minimum Position 1
Use the following menu in the Unit Controller to set “Min


will bring on the corresponding blower speed and allow
damper position adjustment.
  -


-


Note - Intake air CFM can also be determined using the
outdoor air temperature, return air temperature and mixed
air temperature. Refer to the economizer or outdoor air
damper installation instructions.
Set Minimum Position 2
Use the same menu in the Unit Controller to set “Min OCP

        
bring on the corresponding blower speed and allow damp-
er position adjustment.
-


-


Note - Intake air CFM can also be determined using the
outdoor air temperature, return air temperature and mixed
air temperature. Refer to the economizer or outdoor air
damper installation instructions.
TABLE 17
MINIMUM AND MAXIMUM CFM

Unit  

Standard 
Medium 
 

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox LGT Series and is the answer not in the manual?

Lennox LGT Series Specifications

General IconGeneral
BrandLennox
ModelLGT Series
CategoryAir Handlers
LanguageEnglish

Related product manuals