TABLE 5 581115-01
LGT/LCT102
Normal Operating Pressures
Outdoor Coil Entering Air Temperature
65 F 75 F 85 F 95 F 105 F 115 F
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Circuit 1
109 228 111 266 114 312 116 362 118 430 119 502
117 231 119 267 122 312 125 363 127 427 129 497
133 239 137 272 140 314 143 366 146 423 148 490
151 250 155 280 159 319 163 373 166 423 169 487
Circuit 2
124 243 126 280 128 327 130 383 132 448 135 523
132 249 134 285 136 331 139 385 142 449 144 522
150 261 153 294 155 337 158 388 161 449 164 520
170 271 173 301 176 341 179 390 183 448 186 515
70
80
90
100
110
120
Suction Pressure (psig)
Outdoor Temperature (°F)
115°
105°
95°
85°
75°
65°
Charging Curves
Circuit 1
Circuit 2
60
100 110 120 130 140 150 160 170 180 190