EasyManuals Logo

Lennox LHT156 Installation Instructions

Lennox LHT156
38 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #26 background imageLoading...
Page #26 background image
Page 26
LHT/LDT156, 180, 240
Multi-Staged Air Volume Operation
This is a summary of cooling operation. Refer to the
sequence of operation provided in the Engineering
Handbook or Service Manual for more detail.
A-Two-Stage Thermostat
1-Economizer With Outdoor Air Suitable
Y1 Demand -
Compressors Off
Blower Cooling Low
Dampers modulate
Y2 Demand -
Compressors Off
Blower Cooling High
Dampers Modulate
Note - If dampers are at maximum open for three minutes,
compressor 1 is energized low and blower stays on cooling
high.
2-No Economizer or Outdoor Air Not Suitable
Y1 Demand -
Compressor 1 High
Blower Cooling Low
Dampers Minimum Position
Y2 Demand -
Compressor 1 High, Compressor 2 On
Blower Cooling High
Dampers Minimum Position
B-Three-Stage Thermostat
1-Economizer With Outdoor Air Suitable
Y1 Demand -
Compressors Off
Blower Cooling Medium
Dampers Modulate
Y2 Demand -
Compressors Off
Blower Cooling High
Dampers Modulate
Note - If dampers are at maximum open for three minutes,
compressor 1 is energized low and blower stays on cooling
high.
Y3 Demand -
Compressor 1 High
Blower Cooling High
Dampers Maximum Open
2-No Economizer or Outdoor Air Not Suitable
Y1 Demand -
Compressor 1 Low
Blower Cooling Low
Y2 Demand -
Compressors 1 Low, Compressor 2 On
Blower Cooling Medium
Y3 Demand -
Compressors 1 High, Compressor 2 On
Blower Cooling High

Other manuals for Lennox LHT156

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox LHT156 and is the answer not in the manual?

Lennox LHT156 Specifications

General IconGeneral
BrandLennox
ModelLHT156
CategoryHeat Pump
LanguageEnglish

Related product manuals