INSTALLATION
INSTRUCTIONS
©
2016 Lennox Industries Inc.
Dallas, Texas, USA
MLA/MPA/MPB and
M22A/M33A/M33B Series
SINGLE-ZONE MINI-SPLIT SYSTEMS
(208/230V) --
Cassette-Mounted Indoor Unit
507546-06
10/2017
Supersedes 10/2016
WARNING
Improper installation, adjustment, alteration, ser vice or
maintenance can cause property damage, personal
injury or loss of life.
Installation and service must be performed by a li censed
professional HVAC installer (or equivalent) or a service
agency.
WARNING
The clean Air Act of 1990 bans the intentional venting of
refrigerant (CFCs, HCFCs, and HFCs) as of July, 1992.
Approved methods of recovery, recycling or reclaiming
must be followed. Fines and/or incarceration may be
levied for non-compliance.
WARNING
This product contains a chemical known to the State
of California to cause cancer, birth defects, or other
reproductive harm.
CAUTION
As with any mechanical equipment, contact with sharp
sheet metal edges can result in personal injury. Take
care while handling this equipment and wear gloves and
protective clothing.
General
Refer to the Product Specications bulletin (EHB) for more
product information.
These instructions are intended as a general guide and
do not supersede local or national codes in any way.
Authorities having jurisdiction should be consulted before
installation.
The M22A, M33A and M33B ceiling cassette indoor units
are matched with an outdoor heat pump unit to create a
mini-split system that uses HFC-410A refrigerant.
Table of Contents
General ...........................................................................1
Included Parts.................................................................2
Model Number Identication ...........................................3
Indoor / Outdoor Unit Match-Ups....................................4
Typical System Components ..........................................5
System Dimensions ........................................................6
Outdoor Units................................................................6
Indoor Units ..................................................................7
System Clearances ........................................................9
Outdoor Unit .................................................................9
Indoor Unit ....................................................................9
Torque Requirements for Caps and Fasteners.............10
Indoor Unit Installation ..................................................10
Unit Placement Considerations ..................................10
Installation of Cassette Base ......................................10
Installation of M33 Cassette Cover Panel...................11
Indoor Unit Condensate Piping Connections ..............13
Outdoor Unit Installation ...............................................13
Placement Considerations ..........................................13
Direct Sunlight, Rain, Snow and Ice Protection ..........14
Prevailing Winds .........................................................15
Buried Refrigerant Pipe Protection .............................15
Outdoor Unit Condensate Piping ................................15
Securing the Outdoor Unit ..........................................16
Refrigerant Piping Connections ....................................17
Leak Test and Evacuation ............................................18
Leak Test ....................................................................18
Triple Evacuation Procedure .......................................18
Wiring Connections ......................................................19
Outdoor Unit ..............................................................19
Indoor Unit ..................................................................19
Unit Start-Up .................................................................27
Adding Refrigerant for Longer Line Set ........................27
Troubleshooting ............................................................28
Test Run .......................................................................28
Pre-Checks .................................................................28
Procedure ...................................................................28
Dry Mode Operation (Dehumidication) .......................28
Procedure ...................................................................28
Sequence of Operation ...............................................28
THIS MANUAL MUST BE LEFT WITH THE OWNER
FOR FUTURE REFERENCE
Question and Answer IconNeed help?

Do you have a question about the Lennox M33A024S4-2P and is the answer not in the manual?

Lennox M33A024S4-2P Specifications

General IconGeneral
BrandLennox
ModelM33A024S4-2P
CategoryAir Conditioner
LanguageEnglish

Summary

Unit Compatibility and Match-Ups

Installation Clearances

Outdoor Unit Clearance Requirements

Specifies minimum clearances needed around the outdoor unit for proper operation.

Indoor Unit Clearance Requirements

Specifies minimum clearances required for the indoor unit installation.

Fastener Torque and Indoor Unit Installation

Indoor Unit Placement and Installation Guidelines

Covers important considerations for selecting and installing the indoor unit.

Cassette Base and Grille Installation

Cassette Base Suspension Methods

Details how to properly suspend and support the cassette base unit.

Cassette Cover Panel Installation

Cover Panel Alignment and Attachment

Procedures for aligning and securing the cassette cover panel.

Connecting Internal Wiring Harnesses

Steps for connecting the wiring harnesses within the cassette unit.

Outdoor Unit Installation Placement

Securing the Outdoor Unit

Refrigerant Piping and Connections

Refrigerant Line Set Sizing and Specifications

Details on the correct sizes for liquid and gas refrigerant lines.

Making Flare Nut Connections

Step-by-step guide for properly connecting refrigerant lines with flare nuts.

Leak Testing and System Evacuation

Refrigerant System Leak Test Procedure

Detailed steps for performing a leak test on the refrigerant system.

Triple Evacuation Procedure

Wiring Connections

Outdoor Unit Electrical Wiring

Guidelines for making electrical connections to the outdoor unit.

Indoor Unit Electrical Wiring

Guidelines for making electrical connections to the indoor unit.

Single Zone Wiring Diagrams

Indoor Unit Wiring Schematics

MPA Series Outdoor Unit Wiring

MPB Series Outdoor Unit Wiring

MPBMLA Series Outdoor Unit Wiring

Unit Start-Up Procedures

Pre-Start Up Inspection and Checks

Essential checks to perform before energizing the unit.

Adding Refrigerant for Long Line Sets

Guidance on calculating and adding refrigerant for extended pipe lengths.

Troubleshooting and System Operation

Troubleshooting Error Codes

List of error codes and their corresponding descriptions for diagnosis.

Test Run Procedure and Checklist

Steps for performing a test run and a checklist for verification.