EasyManua.ls Logo

Lennox MHA024S4S-1P - 12.1. Leak Checks and Air Purging; 12.2. Refrigerant Management

Lennox MHA024S4S-1P
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
30
12.1. Gas Leak Check with Soap Water:
Apply soap water or a liquid neutral detergent on the
connectionswithasoftbrushtocheckforleakageinthepipe
connectingpoints.Ifbubblesemerge,thepipesareleaking.
12.2. Air and Moisture
Airandmoistureintherefrigerantsystemcausethefollowing
problems:
Increasesinsystempressure
Increasesinoperatingcurrent
Decreasesincoolingandheatingefciency
Blocksincapillarytubingcausedbymoistureinthe
refrigerantcircuitfreezing
Corrosionofpartsintherefrigerantsystemcausedby
water
Theindoorunitsandthepipesbetweenindoorandoutdoor
unitsmustbetestedforleakagesandevacuatedtoremove
gasandmoisturefromthesystem.
12.3. Air Purging using a Vacuum Pump
Completelytightenthearenutsontheindoorand
outdoorunits.Conrmthatboththetwo-wayandthree-
wayvalvesaresettotheclosedposition.
Connectthechargehosewiththepushpinofthe
HandleLotothethree-wayvalvegasserviceport.
ConnectthechargehoseoftheHandleHitothe
vacuumpump.
FullyopentheHandleLoofthemanifoldvalve.
Turnonthevacuumpumptobeginevacuation.
Conducta30-minuteevacuation.Checkwhether
thecompoundmeterindicates-0.1Mpa(14.5Psi).If
themeterdoesnotindicate-0.1Mpa(14.5Psi)after
30minuteshaselapsed,continueevacuationfor20
moreminutes.Ifthepressuredoesnotreach-0.1Mpa
(14.5Psi)after50minuteshaselapsed,checkifthere
areanyleaks.
FullyclosetheHandleLovalveofthemanifoldvalve
andturnoffthevacuumpump.Afterveminutes,
conrmthatthegaugeneedleisnotmoving.
Turnthearenutonthethree-wayvalve45°counter-
clockwisefor6-7seconds.Oncegasbeginstocome
out,tightenthearenut.Makesurethepressure
displayonthepressureindicatorishigherthan
atmosphericpressure.Thenremovethechargehose
fromthethree-wayvalve.
Fullyopenthetwo-wayandthree-wayvalvesand
securelytightenthecaponthethree-wayvalve.
12.4. Adding Refrigerant if Pipe Length Exceeds
Charge Less Pipe Length
Connectthechargehosetothechargingcylinderandopen
the two-way and three-way valves. With the charge hose
youdisconnectedfromthevacuumpump,connectittothe
valveatthebottomofthecylinder.
IftherefrigerantisR-410A,placethecylinderbottom-upto
ensureliquidchargingispossible.
Purgetheairfromthechargehose.
Openthevalveatthebottomofthecylinderandpress
thecheckvalveonthechargeset(becarefulofthe
liquidrefrigerant).
Placethechargingcylinderontotheelectronicscale
andrecordtheweight.
Turnontheairconditionerincoolingmode.
Openthevalves(Lowside)onthechargeset.Charge
thesystemwithliquidrefrigerant.
Whentheelectronicscaledisplaystheproperweight
(refertothetable),disconnectthechargehosefrom
thethree-wayvalve’sserviceportimmediatelyandturn
offtheairconditionerbeforedisconnectingthehose.
MountthevalvestemcapsandtheserviceportUse
atorquewrenchtotightentheserviceportcaptoa
torqueof18N.m(13.27ft·lbs).
Besuretocheckforgasleaks.
12.5. Add Refrigerant after Long-Term System
Operation
Connectthechargehosetothethree-wayserviceport
andopenthetwo-wayandthree-wayvalve.
Connectthechargehosetothevalveatthebottom
ofthecylinder.IftherefrigerantisR-410A,placethe
cylinderbottom-uptoensureliquidcharge.
Purgetheairfromthechargehose.
Openthevalveatthebottomofthecylinderandpress
thecheckvalveonthechargesettopurgetheair(be
carefuloftheliquidrefrigerant).
Placethechargingcylinderontotheelectronicscale
andrecordtheweight.
Turnontheairconditionerincoolingmode.
Openthevalves(Lowside)onthechargesetand
chargethesystemwithliquidrefrigerant.
Whentheelectronicscaledisplaystheproperweight
(refertothegaugeandthepressureofthelowside),
disconnectthechargehosefromthethree-wayvalve’s
serviceportimmediatelyandturnofftheairconditioner
beforedisconnectingthehose.
Mountthevalvestemcapsandtheserviceport.Use
torquewrenchtotightentheserviceportcaptoa
torqueof18N.m(13.27ft·lbs).

Table of Contents

Other manuals for Lennox MHA024S4S-1P

Related product manuals