Condensate Piping
          
       

 -
-


NOTE - If necessary the condensate trap may be installed
up to 5’ away from the furnace. Use PVC pipe to connect
trap to furnace condensate outlet. Piping from furnace
must slope down a minimum of 1/4” per ft. toward trap.
1 -       


NOTE - Do not remove the rubber grommet used to
seal the cabinet on the side not used when installing
the condensate trap.
2 -           


         
      

NOTE - Cold end header box drain plugs are factory
installed. Check the unused plug for tightness to
prevent leakage.
3 -          


       
        
       


 
       
      
 

CONDENSATE TRAP AND PLUG LOCATIONS
(Unit shown in upflow position)
NOTE - In upflow applications where side return
sate trap, filter rack must be installed beyond
condensate trap or trap must be re-located to
avoid interference.
Trap
(same on
right side)
Plug
(same on left side)
1-1/2 in.
FIGURE 45
Upow furnace (FIGURE 51) -

      



Horizontal furnace (FIGURE 52) 





NOTE - In horizontal applications it is recommended
to install a secondary drain pan underneath the unit
and trap assembly.
NOTE - Appropriately sized tubing and barbed tting
may be used for condensate drain. Attach to the
drain on the trap using a hose clamp. See FIGURE
46.
 


Field Provided Drain Components
Tubing
Hose Clamp
Barbed Fitting
Elbow
FIGURE 46