EasyManua.ls Logo

Lennox ML195UH

Lennox ML195UH
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 38
Thermostat Furnace Condensing
Unit
ML195UH and CONDENSING UNIT
THERMOSTAT DESIGNATIONS
(Refer to specific thermostat and outdoor unit.)
COMMON
POWER
HEAT
INDOOR BLOWER
Y
C
R
G
W1
Y
C
R
G
W
COOLING
FIGURE 57
CONDENSING
UNIT
CONDENSING
UNIT COMMON
*CONDENSING
UNIT
*NOTE − R" REQUIRED ON SOME OUTDOOR UNITS
Install the room thermostat according to the instruc-
tions provided with the thermostat. See figure 57 for
thermostat designations. If the furnace is being
matched with a heat pump, refer to the FM21 installa-
tion instruction or appropriate dual fuel thermostat in-
structions.
Indoor Blower Speeds
1 When the thermostat is set to FAN ON," the indoor
blower will run continuously on the heating speed
when there is no cooling or heating demand.
2 When the ML195UH is running in the heating mode,
the indoor blower will run on the heating speed.
3 When there is a cooling demand, the indoor blower will
run on the cooling speed.
Generator Use − Voltage Requirements
The following requirements must be kept in mind when
specifying a generator for use with this equipment:
D The furnace requires 120 volts +
10% (Range: 108
volts to 132 volts).
D The furnace operates at 60 Hz +
5% (Range: 57 Hz to
63 Hz).
D The furnace integrated control requires both polarity
and proper ground. Both polarity and proper grounding
should be checked before attempting to operate the
furnace on either permanent or temporary power.
D Generator should have a wave form distortion of less
than 5% THD (total harmonic distortion).
TYPICAL ML195UH FIELD WIRING DIAGRAM
FIGURE 58
IGNITOR
*R
*NOTE − R" REQUIRED ON SOME OUTDOOR UNITS

Related product manuals