Page 34
Furnace with Evaporator Coil Using a Separate Drain
(Unit shown in horizontal left-hand discharge position)
.
5’ max.
PVC Pipe Only
4”min
5”max
Evaporator
Coil
Drain
Pan
Condensate
DrainConnection
Field Provided Vent
(4” min. to 5” max. above
condensate connection)
Piping from furnace and evaporator coil must slope down a minimum 1/4” per ft. toward trap
(Trap at coil is optional)
Figure 51
Furnace with Evaporator
Coil Using a Common Drain
(1” min.to2 Max.above
condensatedrain connection)
Condensate
Drain
Connection
Evaporator drain
line required
(Trap at coil is optional)
Figure 52
IMPORTANT
When combining the furnace and evaporator coil
drains together, the A/C condensate drain outlet must
be vented to relieve pressure in order for the furnace
pressure switch to operate properly.
Furnace with Evaporator Coil Using a Common Drain
(Unit shown in horizontal left−hand discharge position)
Condensate Drain
Connection
(4” min.to5 Max.above
condensatedrain
connection)
5’ max.
PVC Pipe Only
4”min
5”max
Evaporator
Coil
Drain
Pan
Piping from furnace and evaporator coil must slope
down a minimum 1/4” per ft. toward trap
(Trap at coil is optional)
Figure 53

Other manuals for Lennox ML196UH090XE48C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox ML196UH090XE48C and is the answer not in the manual?

Lennox ML196UH090XE48C Specifications

General IconGeneral
BrandLennox
ModelML196UH090XE48C
CategoryFurnace
LanguageEnglish

Related product manuals