Page 10
TABLE 2 
Diagnostic Codes Red LED
LED Status Description
LED O
No power to control or control har-
ware fault detected.
LED On Normal operation.
1 Flash
Flame present with gas vavle de-en-
ergized.
2 Flashes
Pressure switch closed with combus-
tion air inducer de-energized.
3 Flashes
Low-re pressure, rollout or limit 
switch open.
4 Flashes Primary limit switch open.
5 Flashes Not used
6 Flashes Pressure switch cycle lockout.
7 Flashes Lockout, burners fail to light.
8 Flashes
Lockout, buners lost ame too many 
times.
9 Flashes Line voltage polarity incorrect.
TABLE 3 
Control 5 Pin Terminal Designation
PIN # Function
1 Ignitor (Hot)
2 Combustion Air Inducer High 
Speed
3 Combustion Air Inducer Low Speed
4 Combustion Air Inducer Neutral
5 Ignitor Neutral
Airow Adjustments
Cooling Mode
The units are factory  set for the highest  airow for each 
model. Adjustments can be made to the cooling airow by 
repositioning the jumper plug marked COOL – A, B, C, D 
(see FIGURE 3).   To determine what CFM the motor is de-
livering at any time, count the number of times the amber 
LED on the control board ashes. Each ash signies 100 
CFM; count the ashes and multiply by 100 to determine 
the actual CFM delivered (for example: 5 ashes x 100 = 
500 CFM).
Fan on / o delay
On a call for heat there is a 30 second fan on delay after 
igntion.When  the call  for  heat  is  satised,  the  gas  valve 
and combustion air blower shut down. The circulating air 
blower continues to run for selected blower o delay time 
(60/90/120/180  sec)  before  ramping  down  and  shutting 
o. The fan on delay is 30 seconds and not adjustabe.
NOTE - The fan o delay on ML296-55 and earlier units is 
factory set at 120 seconds and NON- ADJUSTABLE.
TABLE 4 
12 Pin Terminal Designation
Pin # Function
1 Gas Valve Second Stage
2 Second Stage Prove Switch
3 Rollout Switch In
4 Ground
5 24V Hot
6 Primary Limit In
7 Gas Valve First Stage
8 Gas Valve Common
9 24V Neutral
10 Ground
11 Rollout Switch Out
12 First Stage Prove Switch
Heating Mode
These units are factory set to run at the middle of the heat-
ing rise range as shown on the unit rating plate. If higher 
or lower rise is desired, reposition the jumper plug marked 
HEAT - A, B, C, D (see FIGURE 3) . To determine what 
CFM the motor is delivering at any time, count the number 
of times the amber LED on the control board ashes. Each 
ash signies 100 CFM; count the ashes and multiply by 
100 to determine the actual CFM delivered (for example: 
5 ashes x 100= 500.
Adjust Tap
Airow amounts may be increased or decreased by 10% 
by moving the ADJUST jumper plug (see Figure 3) from 
the NORM position to the (+) or (-) position. Changes to 
the ADJUST tap  will  aect both  cooling  and heating  air-
ows. The TEST position on the ADJUST tap is not used.
Continuous Blower Operation
The  comfort  level  of  the  living  space  can  be  enhanced 
when using this feature by allowing continuous circulation 
of air between calls for cooling or heating. The circulation 
of air occurs at half the full cooling airow rate.
To engage the continuous blower operation, place the fan 
switch on the thermostat into the ON position. A call for fan 
from the thermostat closes R to G on the ignition control 
board. The control waits for a 1 second thermostat delay 
before responding to the call for fan by ramping the circu-
lating blower up to 50% of the cooling speed. When the 
call for continuous fan is satised, the control immediately 
ramps down the circulating blower.