Page 44
IV-HEATING SYSTEM SERVICE CHECKS
A-CSA Certication
All  units  are  CSA  design  certied  without  modications. 
Refer to the ML296DFV(X) Installation Instruction.
B-Gas Piping
 CAUTION
If a exible gas connector is required or allowed by 
the authority that has jurisdiction, black iron pipe 
shall be installed at the gas valve and extend outside 
the furnace cabinet. The exible connector can then 
be added between the black iron pipe and the gas 
supply line.
 WARNING
Do not over torque (800 in-lbs) or under torque (350 
in-lbs) when attaching the gas piping to the gas 
valve.
Gas  supply  piping  should  not  allow  more  than  0.5”W.C. 
drop in pressure between gas meter and unit. Supply gas 
pipe must not be smaller than unit gas connection.
Compounds used on gas piping threaded joints should be 
resistant to action of liqueed petroleum gases.
C-Testing Gas Piping
 IMPORTANT
In case emergency shutdown is required, turn o the 
main shut-o valve and disconnect the main power 
to unit. These controls should be properly labeled 
by the installer.
When pressure testing gas  lines, the gas valve must  be 
disconnected and isolated. Gas valves can be damaged if 
subjected to more than 0.5 psig (14” W.C.). See FIGURE 
51. If the pressure is greater than 0.5psig (14”W.C.), use 
the manual shut-o valve before pressure testing to iso-
late furnace from gas supply.
VALVE WILL NOT HOLD
NORMAL TEST PRESSURE
CAP
FURNACE
ISOLATE
GAS VALVE
1/8” N.P. T. PLUGGED TAP
FIGURE 51 
When  checking  piping  connections  for  gas  leaks,  use 
preferred  means.  Kitchen  detergents  can  cause  harmful 
corrosion  on  various  metals  used  in  gas  piping.  Use  of 
a specialty Gas Leak Detector is strongly recommended.
It is available through Lennox under part number 31B2001. 
See Corp. 8411-L10, for further details.
Do  not  use  matches,  candles,  ame  or  any  other 
source of ignition to check for gas leaks.
D-Testing Gas Supply Pressure
An inlet pressure post located on the gas valve provides 
access to the supply pressure. See FIGURE 50. Back out 
the 3/32 hex screw one turn, connect a piece of 5/16 tub-
ing and connect to a manometer to measure supply pres-
sure. See table 21 for supply line pressure.
E-Check Manifold Pressure
NOTE - Pressure test adapter kit (10L34) is available from 
Lennox to facilitate manifold pressure measurement.
A  manifold  pressure  post  located  on  the  gas  valve  pro-
vides access to the manifold pressure. See FIGURE 50. 
Back  out  the  3/32  hex  screw  one  turn,  connect  a  piece 
of 5/16  tubing  and  connect  to  a  manometer  to  measure 
manifold  pressure.  To  correctly  measure  manifold  pres-
sure,  the  dierential  pressure  between  the  positive  gas 
manifold and the negative burner box must be considered.
 IMPORTANT
For  safety,  connect  a  shut-o  valve  between  the 
manometer and the gas tap to permit shut o of gas 
pressure to the manometer.
1 -  Connect the test gauge positive side “+“ to manifold 
pressure tap on gas valve as noted above.
2 -   Tee  into  the  gas  valve  regulator  vent  hose  and 
connect to test gauge negative “-”.
3 -   Ignite unit  on  low  re  and let  run  for  5  minutes to 
allow for steady state conditions.
4 -   After allowing unit to stabilize for 5 minutes, record 
low  re  manifold  pressure  and  compare  to  value 
given in TABLE 21. If necessary, make adjustment. 
FIGURE  50  shows  location  of  low  re adjustment 
screw.
5 -   Repeat on high re and compare to value given in 
TABLE 21. If necessary, make adjustment. FIGURE 
50 shows location of high re adjustment screw.
6 -   Shut unit o and remove manometer as soon as an 
accurate reading has been obtained.
7 -   Start  unit  and  perform  leak  check.  Seal  leaks  if 
found.
The gas valve is factory set and should not require adjust-
ment. All gas valves are factory regulated.
F- Proper Gas Flow (Approximate)
Furnace should operate at least 5 minutes before check-
ing  gas  ow.  Determine  time  in  seconds  for  two  revolu-
tions of gas through the meter. (Two revolutions assures 
a  more  accurate  time.)  Divide by two  and  compare  to 
time  in TABLE  18.  If  manifold  pressure  matches TABLE 
21 and rate is incorrect, check gas orices for proper size 
and restriction.