EasyManua.ls Logo

Lennox MLA024S4S-1P - Page 135

Lennox MLA024S4S-1P
168 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
135
Error Code: EE
Description: Water-levelalarmmalfunction.(ForM22A,M33A/BandMMDAunits)
General Note: Ifthesamplingvoltageisnot5V,theLEDwilldisplaythefailure.
Poweroff,thenrestarttheunit3minutes
later.Isitstilldisplayingtheerrorcode?
Ifthewater-levelswitchisinsertedwell?
Yes
No
No
Insertthewater-level
switchwell.
Ifthewater-levelswitchisbroken?
Replacethewaterpump,Ifmalfunctionis
still not solved.
ReplacetheindoormainPCB.
Yes
Replacethewater-level
switch.

Table of Contents

Other manuals for Lennox MLA024S4S-1P

Related product manuals