26
Remote Control Terminal
(ON-OFF, CN2, Short Connector JR1) 
NOTE:   Remove the short connector (JR1) when using the ON-OFF function. 
Remote Switch Unit Status Demand Response Time
ON (close) 
1
Unit is on.  Within two (2) seconds
OFF (open) 
2
Unit is o. Within two (2) seconds
1. Unit responds to demand; use the remote controller to select the required mode.
2. Unit will not respond to the demand from the remote controller. 
NOTE:  If the remote switch is o, but the remote controller is on, the CP code appear on the display board. 
NOTE:  The voltage of the port (CN2) is 12V DC; maximum current is 5mA.
4.5.  Dial Codes
NOTE:  The SW4 DIP switch is for certied service technical use only.
No. Dial Code Control 
Scenario
Function ON OFF Note
1 SW1-2 1,2 Anti-cold blow protection option NO [Default] YES
2 SW1-3 1,2,3 Single cooling / heating and cooling options Cooling [Default] Cooling & 
Heating
3 SW2-1 1 Compressor Running (demand working with 
heat pump+ Electric heat)
Compressor 
slower speed
[Default] Faster 
Compressor
Only aects 
compressor and 
W1
4 SW2-1 2 Temperature dierential to activate rst stage 
auxiliary heat(the GAP of T1 and Ts),Wire 
controller demand with heat pump+Electric heat 
working together
2°F (1°C) [Default] 4°F (2°C)
5 SW2-2 2 Electric heat on delay YES [Default]NO
6 SW2-3 2 Electric auxiliary heating delay to start time 30 minutes [Default] 15 
minutes
Based on SW2-2 
is ON