AIR FOR COMBUSTION AND VENTILATION
Contaminated Combustion Air:
This furnace is not to be installed in a structure
defined as having contaminated combustion air. Allowing
exposure to substances containing chlorine or fluoride
could harm the furnace and void the warranty.
Substances to avoid include, but are not limited to:
Permanent wave solutions
Chlorinated waxes and cleaners
Chlorine based swimming pool chemicals
Water softening chemicals
De-icing salts or chemical
Carbon tetrachloride
Halogen type refrigerants
Cleaning solvents (such as perchloroethylene)
Printing inks, paint removers, varnishes, etc.
Hydrochloric acid
Cements and glues
Antistatic fabric softeners for clothes dryers
Masonry acid washing materials
Unrefined gases
Contaminated combustion air may cause premature
failure of the heat exchanger that may lead to a
hazardous condition and/or bodily harm, or loss of
life.
Adequate Ventilation and Combustion Air:
This section is provided to give guidelines for the
introduction of air for ventilation and combustion air. The
total quantity of air provided to the installation area must
equal the requirements of all gas appliances in the area.
Adequate facilities for providing air for combustion
and ventilation must be provided in accordance with the
latest edition of the National Fuel Gas Code ANSI
Z223.1/NFPA54 or CSA B149.1 Natural Gas and Propane
Installation Codes, or applicable provisions of the local
building codes.
The furnace shall be installed in a location in which
the facilities for ventilation permits satisfactory combustion
of gas, proper venting and maintenance of ambient
temperature at safe limits under normal conditions of use.
The furnace shall be located so as not to interfere with
proper circulation of air.
In addition to air needed for combustion, ventilation in
the form of process air must be provided as required for:
cooling of equipment or material, controlling dew point,
heating, drying, oxidation or dilution, safety exhaust and
odor control. Air must be supplied for ventilation,
including all air required for comfort and proper working
conditions for personnel.
For purposes of this instruction the following
definitions apply:
Confined Space: A space whose volume is less
than 50 cubic feet per 1000
Btu/hr of the aggregate input
rating of all appliances installed
in that space.
Unconfined Space: A space whose volume is not
less than 50 cubic feet per 1000
Btu/hr of the aggregate input
rating of all appliances installed
in that space. Rooms
communicating directly with the
space in which the appliances
are installed, through openings
not furnished with doors, are
considered a part of the
unconfined space.
If the installation area meets the definition of
"Unconfined Space" and does not have additional air
requirements as described, the furnace may be installed
without making special provisions for combustion and
ventilation air.
Whenever this furnace is installed in an area along
with one or more gas appliances, the total Btu/hr
input of all appliances must be included when
determining the free area requirements for
combustion and ventilation air openings.
Do not block the combustion or ventilation air
openings in the furnace. Any blockage will result in
improper combustion and may result in a fire
hazard or unsafe condition.
20541501 Issue 0240 Page 8 of 26

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox MPGA 100 B4 and is the answer not in the manual?

Lennox MPGA 100 B4 Specifications

General IconGeneral
BrandLennox
ModelMPGA 100 B4
CategoryFurnace
LanguageEnglish

Related product manuals