Table 18. Ventilation Control Modes
Ventilation Control Mode
Fresh Air
Damper
1
Speed
HRV
2
Speed
HRV
1
Speed
ERV
2
Speed
ERV
ASHRAE Number of Bedrooms X X X X X
Ventilation Outdoor Condition Override - Enabled
Ventilation High Outdoor Temperature Limit
(60 to 115°F, default is 100°F)
X X X X X
Ventilation Low Outdoor Temperature Limit
(–20 to 55°F, default is 0°F)
X X X X X
Ventilation High Outdoor Dew Point Limit
(45 to 80°F, default is 55°F)
X X X X X