Table 21. Lennox S40 Smart Thermostat Alert Codes and Troubleshooting
E2A=Errors to Action, GF= Gas Furnace, AH=Air Handler, IU=Indoor unit (GF or AH), HP=Heat Pump, AC=Air Conditioner, OU=Outdoor Unit (AC or HP), PA=Pure Air S, ZA=Zone system,
SRS=Smart Room Sensor, TS=Thermostat , IAQ- IAQ Monitor and WE=Wi-Fi Extender
Alert
Code
Inverter
Flash
Code
Priority
Condition
Actual Displayed Alert
Text Under dealer control
center > Notications
Component or System Operational State and Troubleshooting Tip
How to clear
alert code
71510
Service
Soon
OU: ID TXV Failure
Super Heat average is not in expected range. (Too high or too low superheat)
Replace Expansion Valve.
Automatically clears
when the system
detects that the issue
no longer exists.
71511
Service
Soon
IU: Duct or Filter
Blockage
Clean ducts or replace lter.
Automatically clears
when the system
detects that the issue
no longer exists.
71512
Service
Urgent
OU: High-Pressure
Switch Fault
If switch tripped without meeting the liquid pressure condition.
If Liquid pressure > 500 psig then replace high-pressure switch.
Automatically clears
when the system
detects that the issue
no longer exists.
71513
Service
Soon
OU: Low-Pressure
Switch Fault
If switch tripped without meeting the suction pressure condition.
Replace low-pressure switch.
Automatically clears
when the system
detects that the issue
no longer exists.
71514
Service
Soon
OU: System Low on
Refrigerant Charge
If sub cooling average is not within expected range for given ODT and compressor Hz.
Add refrigerant
Automatically clears
when the system
detects that the issue
no longer exists.
71515
Service
Urgent
HP: Reversing Valve
Stuck
If liquid and suction pressure average ratio does not fall within the expected range.
Service reversing valve message.
Automatically clears
when the system
detects that the issue
no longer exists.
71516
Service
Urgent
OU: Outdoor Fan
Motor Failure
If superheat suction pressure values are not within expected range.
Service outdoor fan.
Automatically clears
when the system
detects that the issue
no longer exists.
71517
Service
Urgent
IU: Indoor Fan Motor
Failure
If superheat suction pressure values are not within expected range.
Service indoor fan.
Automatically clears
when the system
detects that the issue
no longer exists.
71518
Service
Urgent
OU: Compressor
Failed to Start
If liquid and suction pressure average ratio does not fall within the expected range.
Service compressor.
Automatically clears
when the system
detects that the issue
no longer exists.
71519
Service
Urgent
HP: Incorrect
Reversing Valve Mode
If Outdoor coil temperature plus 3°F is less than outdoor temperature or if ODT plus 3°F is greater than
ODT Coil temperature along with Reverse valve status open/closed.
Check solenoid wiring for reverse valve.
Automatically clears
when the system
detects that the issue
no longer exists.