Page 43
A-Heat Exchanger and Burners
Cleaning the Heat Exchanger and Burners
NOTE - Use papers or protective covering in front of the 
furnace during cleaning.
1 -   Turn  o  both  electrical  and  gas  power  supplies  to 
furnace.
2 -   Remove ue pipe, top cap, ue chase and internal 
ue pipe assembly from the unit.
3 -   Label  the  wires  from  gas  valve,  rollout  switches, 
primary  limit  switch  and  make-up  box  then 
disconnect them.
4 -   Remove the screws that secure the combustion air 
inducer  pressure switch assembly to the collector 
box.  Carefully  remove  the  combustion  air  inducer 
to  avoid  damaging  blower  gasket.  If  gasket  is 
damaged, it must be replaced to prevent leakage.
5 -   Remove  the  collector  box  located  behind  the 
combustion air inducer. Be careful with the collector 
box  gasket.  If  the  gasket  is  damaged,  it  must  be 
replaced to prevent leakage.
6 -   Disconnect  gas  supply  piping.  Remove  the  screw 
securing  the  burner  box  cover  and  remove  cover. 
Remove  the  four  screws  securing  the  burner 
manifold  assembly  to  the  vestibule  panel  and 
remove the assembly from the unit.
7 -   Remove  screws  securing  burner  box  and  remove 
burner box.
8 -   Remove screws from both sides, top and bottom of 
vestibule panel.
9 -   Remove  heat  exchanger.  It  may  be  necessary 
to  spread  cabinet  side  to  allow  more  room.  If  so, 
remove ve screws from the left side or right side of 
cabinet. See FIGURE 22.
         BURNER, C.A.I ASSEMBLY &
HEAT EXCHANGER REMOVAL
heat exchanger
gasket
collector box
orifice plate
internal flue pipe
pressure switch
combustion air inducer
burner box cover plate
manifold and gas valve
gasket
retention rings
cross over
gasket
rollout switch
sensor
rollout switch
(alternate location)
Sight glass
FIGURE 21