BLOWER DATA
SL280UH110V60C BLOWER PERFORMANCE (less lter)
BOTTOM RETURN AIR, RETURN AIR FROM BOTH SIDES OR RETURN AIR FROM BOTTOM AND ONE SIDE
0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
HEATING
1
Heating Speed
DIP Switch
Settings
First Stage Heating Speed - cfm Second Stage Heating Speed - cfm
+24% 1690 1855
+18% 1605 1765
+12% 1525 1675
+6% 1445 1585
Factory Default 1360 1495
–6% 1280 1405
–12% 1200 1315
–18% 1115 1230
COOLING
1
Cooling Speed
DIP Switch
Settings
First Stage Cooling Speed - cfm Second Stage Cooling Speed - cfm
Low Medium-Low Medium-High
2
High Low Medium-Low Medium-High
2
High
+ 1060 1220 1330 1565 1535 1710 1910 2210
Factory Default 970 1075 1180 1430 1400 1565 1715 2015
– 875 980 1070 1255 1260 1400 1560 1815
BLOWER DATA
SL280UH135V60D BLOWER PERFORMANCE (less lter)
BOTTOM RETURN AIR, RETURN AIR FROM BOTH SIDES OR RETURN AIR FROM BOTTOM AND ONE SIDE
0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
HEATING
1
Heating Speed
DIP Switch
Settings
First Stage Heating Speed - cfm Second Stage Heating Speed - cfm
+24% 1875 2065
+18% 1785 1965
+12% 1695 1865
+6% 1605 1765
Factory Default 1515 1665
–6% 1425 1565
–12% 1330 1465
–18% 1240 1365
COOLING
1
Cooling Speed
DIP Switch
Settings
First Stage Cooling Speed - cfm Second Stage Cooling Speed - cfm
Low Medium-Low Medium-High
2
High Low Medium-Low Medium-High
2
High
+ 1025 1120 1325 1650 1500 1600 1840 2235
Factory Default 965 1015 1180 1490 1420 1510 1700 2110
– 875 930 1060 1350 1225 1320 1505 1840
1
Cooling and heating speeds are based on a combination of DIP switch settings on the furnace control. Refer to Installation Instructions for specic DIP Switch Settings.
2
Factory default setting.
NOTES - The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage HEAT.
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan Only speed is selectable at 28%, 38%, 70% and 100% of the selected second stage cooling speed - minimum 450 cfm.
Lennox iHarmony
®
Zoning System Applications - Minimum blower speed is 450 cfm.