Page 39
F- Proper Gas Flow (Approximate)
Furnace should operate at least 5 minutes before check-
ing  gas  ow.  Determine  time  in  seconds  for  two  revolu-
tions of gas through the meter. (Two revolutions assures 
a more accurate time.) Divide by two and compare to time 
in TABLE 18 below. If manifold pressure matches TABLE 
20 and rate is incorrect, check gas orices for proper size 
and restriction.
NOTE- To obtain accurate reading, shut o all other gas 
appliances connected to meter.
TABLE 18 
GAS METERING CLOCKING CHART
SL280 
Unit
Natural 1000 btu/cu ft LP 2500 btu cu/cu ft
Seconds For One Revolution
1 cu ft dial 2 cu fr dial 1 cu ft Dial 2 cu ft Dial
-070 55 110 136 272
-090 41 82 102 204
-110 33 66 82 164
 IMPORTANT
.For safety, shut unit o and remove manometer as soon 
as an accurate reading has been obtained. Take care to 
replace pressure tap plug.
G- Proper Combustion
Furnace should operate minimum 15 minutes with correct 
manifold pressure and gas ow rate before checking com-
bustion.
See sections E- and F-. Take combustion sample beyond 
the ue outlet and compare to the table below. The max-
imum  carbon  monoxide  reading  should  not  exceed  100 
ppm.
TABLE 19 
Firing Rate CO2% For Nat CO2% For L.P.
High Fire 6.0 - 7.4 6.9 - 8.4
Low Fire 4.8  - 6.0 5.7 - 7.0
The carbon monoxide reading should not exceed 100 ppm.
H-High Altitude
The  manifold  pressure,  gas  orice  and  pressure  switch 
may require adjustment or replacement to ensure proper 
operation at higher altitudes. See TABLE 20 for manifold 
pressures, TABLE 21 for pressure switch kits and TABLE 
22 or TABLE 23 for gas conversion kits.