Page 52
CONDENSATE ASSEMBLY
FIGURE 41
Condensate Drain
Connection In Unit
5 Feet
Maximum
90° PVC Elbow
(field−provided)
90° PVC Elbow
(field provided)
To
Drain
Clean Out
Drain Trap
Assembly
(furnished)
Adapter
1/2" slip X 1/2"
NPT
(field−provided)
Cap and Clamp
Field−Provided
Vent
Out
FIGURE 42
Drain
SLP98UHV with Evaporator Coil
Condensate trap and
evaporator coil must
be drained separately
as shown.
Field−Provided
Vent
FIGURE 43
CONDENSATE TRAP LOCATIONS
(Unit shown in horizontal righthand discharge position)
*5’ max.
to drain
PVC Pipe Only
4−1/2"
Min.
Field−Provided Vent
Must Not Interfere With
Service To The Unit
*Piping from furnace must slope down a minimum of 1/4" per ft. toward trap.
CAUTION
A separate drain line must be run to the drain from
the condensate trap. DO NOT connect the con-
densate trap drain into the drain line from the
evaporator coil.