SLP98UHV / Page 27
BLOWER DATA
SLP98UH090XV48C BLOWER PERFORMANCE (less lter)
SINGLE SIDE RETURN AIR
HEATING BLOWER PERFORMANCE - 0 through 0.8 in. w.g. External Static Pressure Range
Heating Adjust CFM Selections
Heating Input Range and Blower Volume - CFM
35% 40% 50% 60% 70% 80% 90% 100%
Increase (+15%) Heat CFM 747 812 943 1073 1204 1334 1465 1595
Increase (+7.5%) Heat CFM 698 759 882 1005 1127 1250 1372 1495
Default Heat CFM 649 706 821 936 1051 1165 1280 1395
Decrease (-7.5% ) Heat CFM 589 644 755 867 978 1089 1200 1312
Decrease (-15% ) Heat CFM 528 582 690 797 905 1013 1120 1228
COOLING BLOWER PERFORMANCE - 0 through 1.0 in. w.g. External Static Pressure Range
Cooling Adjust CFM
Selections
Blower Speed Selections
First Stage Cool Speed - cfm Second Stage Cool Speed - cfm
Low Medium-
Low
Medium
High
High
(Default)
Low Medium-
Low
Medium
High
High
(Default)
Increase (+10%) Cool CFM 820 1005 1135 1290 1140 1340 1525 1725
Default Cool CFM 755 880 1025 1150 1040 1235 1395 1565
Decrease (-10%) Cool CFM 680 815 925 1065 910 1120 1275 1400
SLP98UH090XV48C BLOWER MOTOR WATTS - COOLING
Blower Speed
Options
Motor Watts @ Various External Static Pressures - in. wg.
First Stage Second Stage
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Increase (+10%) Cool CFM
Low 43 65 85 96 119 134 156 179 199 102 131 155 189 216 249 282 304 331 359 387
Medium-Low 66 95 113 140 164 189 212 242 268 173 196 242 271 306 337 362 405 430 460 493
Medium-High 95 126 151 180 210 242 277 302 320 243 277 316 371 412 457 492 534 566 605 651
High 143 166 203 243 282 309 333 368 389 368 410 453 511 562 604 651 690 730 771 809
Default Cool CFM
Low 36 48 73 86 108 120 140 152 168 75 101 125 156 178 215 244 259 288 320 339
Medium-Low 52 75 95 110 130 161 176 201 216 129 154 190 218 257 295 322 346 377 404 434
Medium-High 70 94 125 146 172 198 230 252 275 190 222 270 299 325 368 398 439 470 508 549
High 100 131 162 197 228 260 298 328 347 275 310 359 400 445 469 525 562 597 642 682
Decrease (-10%) Cool CFM
Low 32 45 58 80 97 110 121 133 154 62 87 109 129 152 173 199 221 250 266 295
Medium-Low 45 63 82 99 119 137 150 171 193 95 124 150 180 207 240 269 297 325 356 375
Medium-High 55 82 101 119 145 167 192 213 239 148 177 205 244 286 309 346 370 402 431 467
High 76 101 137 160 188 218 245 271 302 198 239 274 308 349 384 426 471 500 542 576
The effect of static pressure is included in air volumes shown.
The following control congurations are available. See Installation Instructions for details and DIP switch settings.
Heat Modes Available (Heating Blower Performance Table):
Single stage thermostat:
- 35%, 70%, 100% input (three-stage) with time delays in-between
Two-stage thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts ring rate based on rst- and second-stage cycle times
- W1 demand at 70% input, W2 demand at 100% input. No delay between stages
Cool Mode Available (Cooling Blower Performance table):
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan speeds are approximately 28%, 38%, 70% and 100% (DIP switch selectable) of the same second-stage COOL speed position
minimum 300 cfm.
Lennox Harmony III™ Zoning System Applications - Minimum blower speed is 380 cfm.