EasyManuals Logo

Lennox SLP99DFV Series User Manual

Lennox SLP99DFV Series
75 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #29 background imageLoading...
Page #29 background image
Page 29
C-Heating Components (FIGURE 14)
1. Ignitor
The SureLight
®
ignitor is made of durable silicon nitride.
Ignitor longevity is enhanced by controlling voltage to the
ignitor. The integrated control provides a regulated 120
volts to the ignitor for a consistent ignition and long ig-
nitor life. Due to this feature of the control, voltage mea-
sured with a digital meter will be slightly lower. To measure
correct voltage use a true RMS meter or ignitor can be
ohmed. Ohm value should be 39 to 70.
2. Flame Sensor
A ame sensor is located on the left side of the burner
support. The sensor is mounted on the ame rollout plate
and the tip protrudes into the ame envelope of the left-
most burner. The sensor can be removed for service with-
out removing any part of the burners. During operation,
ame is sensed by current passed through the ame and
sensing electrode. The SureLight control allows the gas
valve to remain open as long as ame signal is sensed.
To check ame sense signal use the push-button found
on the integrated control and go to Field Test Mode. The
menu will display the ame signal. TABLE 18 shows the
ame signal for the SLP99DFV unit.
TABLE 18
Flame Signal in Microamps
Normal Low Drop Out
2.6 or greater 2.5 or less 1.1
NOTE - A much higher than normal micro amp reading
(15 for example) may appear when checking ame signal.
3. Flame Rollout Switches
Flame rollout switch S47 is a high temperature limit located
inside the burner box. Each furnace is equipped with two
identical switches. The limit is a N.C. SPST manual-reset
limit connected in series with the primary limit S10.
When S47 senses rollout, the circuit breaks and the inte-
grated control immediately stops ignition and closes the
gas valve. If unit is running and ame rollout is detected,
the gas valve will close and integrated control will be dis-
abled. Rollout can be caused by a blocked heat exchang-
er, ue or lack of combustion air. The switch is factory set
to trip (open) at 210°F and cannot be adjusted. The switch
can be manually reset. To manually reset a tripped switch,
push the reset button located on the center of the switch.
4. Burners
All units use inshot burners. Burners are factory set and
require no adjustment. Always operate the unit with the
burner box front panel in place. Each burner uses an ori-
ce that is precisely matched to the burner input. Burners
can be removed as a one piece assembly for service. If
burner assembly has been removed, it is critical to align
center of each burner to the center of the clamshell when
re-installing. See more detail in Section VII- MAINTE-
NANCE..
5. Duralock Plus Heat Exchanger (FIGURE 15)
Units use an aluminized steel primary and stainless steel
secondary heat exchanger assembly. Heat is transferred
to the air stream from all surfaces of the heat exchanger.
The shape of the heat exchanger ensures maximum e󰀩-
ciency.
The combustion air inducer pulls fresh air through the
burner box. This air is mixed with gas in the burners. The
gas / air mixture is then burned at the entrance of each
clamshell. Combustion gases are then pulled through the
primary and secondary heat exchangers and exhausted
out the exhaust vent pipe.

Other manuals for Lennox SLP99DFV Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox SLP99DFV Series and is the answer not in the manual?

Lennox SLP99DFV Series Specifications

General IconGeneral
BrandLennox
ModelSLP99DFV Series
CategoryFurnace
LanguageEnglish

Related product manuals