Page 84
XP25
Emergency 24VAC System Operation
The Y and O terminals located on the outdoor control allow the outdoor unit to be cycled ON and OFF using 24VAC inputs. The
outdoor unit will operate at 100% capacity in this configuration.
NOTE - Defrost operation will not have any indoor discharge air tempering due to the lack of a W1 out terminal.
The following wiring diagrams display the wiring changes needed to switch a full communicating system to a partial
communicating system with the XP25 running in emergency mode (24VAC inputs to outdoor unit).
Communicating Air
Handler or
Furnance
24VAC Thermostat
RSBus
Communicating Air
Handler or
Furnance
iComfort WiFi
THERMOSTAT
NOTE 1
C
Y
R
XP25 UNIT
O
XP25 UNIT
NOTES:
1. Move two wires on both indoor and outdoor controls from terminals i+ to Y1 and i- to O for 24VAC operation on heat pump and indoor unit.
2. Do not disconnect wires from the XP25 R and C terminals, both are required.
3. Cut R to O link on indoor control.
NOTE 2
iComfort Wi-Fi
®
Thermostat
Communicating Air Handler and XP25
XC25 XP25
CUT LINK
DO NOT CUT
NOTE 3
Emergency 24VAC
(Non-Communicating Mode)
Figure 62. Thermostat Communication Mode