108
Code Name Parameter
(Factory setting printed in bold)
Acceptance see
page
Your
settings
C210* Preselection:
Process step
-1- Process step 1
-2- Process step 2
... ...
-8- Process step 8
SH + PRG 94
C211* Set-value for
C210
-0- Set-value 1 (C046)
-1- JOG 1
-2- JOG 2
... ...
-15- JOG 15
SH + PRG 94
C212* Pair of ramp
times for C210
-0- Standard pair of ramp times
(C012 and C013)
-1- Additional pair of ramp times 1
-2- Additional pair of ramp times 2
... ...
-15- Additional pair of ramp times 15
SH + PRG 94
C213* Duration for
C210
10.0s 0.0...9900s
(in steps of 10ms from 0.0 to 1s
in steps of 100ms from 1 to 10s
in steps of 1s from 10 to 100s
in steps of 10s from 100to 990s
in steps of 100s from 1000 to 9900s)
ON-LINE 94
C214* Next step for
C210
-0- Finish process control
-1- Process step 1
-2- Process step 2
... ...
-8- Process step 8
SH + PRG 94
C220 Acceleration
time for set-
value 2
5.0s 0.0...990s
(in steps of 10ms from 0.0 to 1s
in steps of 100ms from 1 to 10s
in steps of 100ms from 10 to 990s)
ON-LINE 66
C221 Deceleration
time for set-
value 2
5.0s 0.0...990s
(in steps of 10ms from 0.0 to 1s
in steps of 100ms from 1 to 10s
in steps of 100ms from 10 to 990s)
ON-LINE 66
C234* Load change
damping
0.25 0.00...5.00
(in steps of 0.01)
ON-LINE 96
C238 Frequency
pilot control
-0- No pilot control
-1- With set-value pilot control
-2- With feedback pilot control
[SH + PRG] 74
C239 Frequency
setting range
-0- Frequency setting range bipolar
-1- Frequency setting range unipolar
[SH + PRG] 93
C240 Window
Feedback =
set-value
0.5% 0.0...100%
(in steps of 0.1%)
ON-LINE 88,
77
C241 Window ramp
generator
output = input
0.5% 0.0...100%
(in steps of 0.1%)
ON-LINE 87
C249* Code bank
(only for
LECOM)
0 0...7 SH + PRG 111
C370* Enable
automation
interface
(LECOM2)
-0- No communication via automation
interface
-1- Communication via automation
interface enabled
[SH + PRG] 111
C380 Set-value 1
(Process
datum only for
LECOM)
-16384...+16384
(in steps of 1)
112
C381 Total set-value
(process
datum only for
LECOM)
-16384...+16384
(in steps of 1)
1112
C382 Feedback fo
PI controller
(process
datum only for
LECOM)
-16384...+16384
(in steps of 1)
112