5.2.3 Description of the analog inputs and outputs
Analog inputs
Terminal Switch setting Use
(factory setting)
Level/Resolution Parameter
setting see
page
1, 2 Set-value 2 -10V...+10V
12bit + sign
66
3, 4
ON
OF
F
S1
123
Actual value -10V...+10V
12bit + sign
73 and 66
Actual value -30V...+30V
12bit + sign
73 and 66
Actual value -60V...+60V
12bit + sign
73 and 66
Actual value -90V...+90V
12bit + sign
73 and 66
Actual value -120V...+120V
12bit + sign
73 and 66
7 internal ground (GND)
8 Set-value 1, Master
voltage
-10V...+10V
12bit + sign
64
Set-value 1,
master current
-20mA...+20mA or
±4...20mA
64 and 66
9 Voltage supply for
potentiometer
+10V/7mA
10 Voltage supply for
potentiometer
-10V/7mA
Analog outputs (monitor outputs)
Terminal Switch setting Use
(factory setting)
Level Parameter
setting see
page
60 internal ground (GND)
62 Monitor 1 (Output
frequency)
-10V...+10V 89
Monitor 1 (output
frequency)
-20mA...+20mA 89
63 Monitor 2 (output current) -10V...+10V 89
Monitor 2
(output current)
-20mA...+20mA 89
5.2.4 Description of other inputs and outputs
Terminal Use
(factory setting)
Parameter
setting see
page
11, 12 Input for temperature monitoring of the connected motor
(PTC thermistor/thermal contact)
If a thermistor/thermal contact is not used:
- Link terminals 11 and 12 or deactivate function
97
K11, K14 Relay output, Contact capacity: 50V/0.5A
(Trip fault indication)
86
VE9 Supply input for connected incremental encoder (X5/X8)
GND internal ground (GND)
FE Functional earth