120
4 Checking the power stage
The measurements described below are to be carried out only by
skilled specialists. Use a digital voltmeter. The measuring values
indicate the nominal value. If they are different, there is a defective.
4.1 Checking the mains rectifier
Disconnect inverter from the mains and wait until the DC bus has
discharged (approx. 3 minutes). You can measure directly at the
power terminals.
Measurement Measuring point Measuring value
Diodes in forward
direction
L1 +UG
L2 +UG
L3 +UG
-UG L1
-UG L2
-UG L3
0.4V
0.4V
0.4V
0.4V
0.4V
0.4V
Diodes in reverse
direction
+UG L1
+UG L2
+UG L3
L1 -UG
L2 -UG
L3 -UG
high-resistance (OL)
high-resistance (OL)
high-resistance (OL)
high-resistance (OL)
high-resistance (OL)
high-resistance (OL)
4.2 Checking the power stage
Disconnect inverter from the mains and wait until the DC bus has
discharged (approx. 3 minutes).
You can measure directly at the power terminals.
Measurement Measuring point Measuring value
Inverter diode
in forward direction
U +UG
V +UG
W +UG
0.4V
0.4V
0.4V
Diodes in reverse
direction
UG U
UG V
UG W
high-resistance
high-resistance
high-resistance
Inverter diode in forward
direction
-UG U
-UG V
-UG W
0.4V
0.4V
0.4V
Inverter diode
in reverse direction
U -UG
V -UG
W -UG
high-resistance
high-resistance
high-resistance
4.3 Checking the voltage supply on the control
board 8602MP
Inhibit controller
Remarks Measuring point Measuring value
+Vcc 15 Term. 20 Term. 40 +14.25 V...+15.75 V
+Vref 10 V Term. 9 Term. 40 +9.79 V...+10.21 V
-Vref 10 V Kl. 10 Term. 40 -9.79 V... -10.21 V