Parameter setting with the XT EMZ9371BC keypad
Transfer parameters to other controllers
9
Parameter setting
9.4
9.4.5
L
9.4-7
EDS82EV903-1.0-11/2002
Step Keys Action
1. Connect keypad to controller 2
2. Inhibit controller
S
The drive is idling
3. Select the submenu 7.1 ”Load/Store”
in the menu 7 ”Param managm”
zyZY
Change to the submenu ”Load/S tore” with the arrow
keys
4. Change to the code level
Z
Display C0002 ”Para m managm”
5. Change to parameter level
V
Display ”0” and ”READ Y”
6. Select the correct copy function The settings stored in the controller or in the function
module are overwritten.
• Copying all parameter sets available (PAR1 ... PAR4, ggf. FPAR1) to the controller:
– Controller with function module
application I/O, INTERBUS,
PROFIBUS-DP, LECOM-B,
DeviceNet/CANopen
z
Copy PAR1 ... PAR4 und FPAR1:
ð Set ”70” ”Key->F1&PAR1-4”
– Controller with a ll other function
modules
Copy PAR1 ... PAR4:
ð Set ”10” ”Keypad->PAR1-4”
• Copying single parameter sets (PARx und ggf. FPAR1) to the controller:
– Controller with function module
application I/O, INTERBUS,
z
Copy PAR1 and FPAR1:
ð Set ”71” ”Key->FP1&PAR1”
PROFIBUS-DP, LECOM-B,
DeviceNet/CANopen
Copy PAR2 and FPAR1:
ð Set ”72” ”Key->FP1&PAR2”
Copy PAR3 and FPAR1:
ðSet ”73” ”Key->FP1&PAR3”
Copy PAR4 and FPAR1:
ðSet ”74” ”Key->FP1&PAR4”
– Controller with a ll other function
modules or controller without
Copy PAR1:
ð Set ”11” ”Keypad->PAR1”
function module
Copy PAR2:
ð Set ”12” ”Keypad->PAR2”
Copy PAR3:
ð Set ”13” ”Keypad->PAR3”
Copy PAR4:
ð Set ”14” ”Keypad->PAR4”
• Copying only the module-specific parameter set FPAR1 to the function module:
– Only possible for controllers with
function module INTERBUS,
PROFIBUS-DP, LECOM-B,
DeviceNet/CANopen:
z
Copy FPAR1:
ð Set ”40” ”Keypad->FPAR1”
7. Start copying
TV
The selected parameter sets are copied to the
controller or the function module.
”LOADING...” i s indicated.
If ”LOADING...” stops, the copy process is co mple ted.
8.
Change to the code level
A)
V
Display of operation level
B)
V
Display C0002 ”Para m managm”
9. Enable the controller.
U
The drive should be running again
Copying parameter sets from the