6.3 Measures when drive is used in IT systems
If the drive is installed in an IT system, internal filters must be separated from
the PE conductor.
How to proceed:
1. With a controller already mounted: Switch off mains voltage!
2. Remove the small cap on the top.
3. Unscrew and remove the screw.
4. Screw in cap.
IT system