EasyManua.ls Logo

Lenze ESV552N02TXB571

Lenze ESV552N02TXB571
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
20
EDBSV571 EN 1.0
EN
Commissioning
4.5 Parameter Menu
4.5.1 Basic Setup Parameters
Code Possible Settings
IMPORTANT
No. Name Default Selection
P100
Start Control
Source
0 0 Local Keypad Use RUN button on front of drive to start
1 Terminal Strip Use start/stop circuit wired into the terminal
strip. Refer to section 3.2.3
2 Network Only • Start command must come from network
(Modbus, CANopen, etc)
• SMV models <15HP (11kW) require optional
communication module (refer to the
network module documentation).
WARNING!
P100 = 0 disables TB-1 as a STOP input! STOP circuitry may be disabled if parameters
are reset back to defaults (see P199)
NOTE
• The STOP button on the front of the drive is always active except in JOG mode.
• TB-1 is an active STOP input if P100 is set to a value other than 0.
P101
Standard
Reference
Source
0 0 Keypad (Local or Remote) Selects the default speed or torque reference
when no Auto Reference is selected using the
TB-13 input.
1 0-10 VDC
2 4-20 mA
3 Preset #1 (P131)
4 Preset #2 (P132)
5 Preset #3 (P133)
6 Network
7 Preset Sequence Segment #1 (P710) Selections 7, 8 & 9 are not valid for PID
setpoint or torque reference.
8 Preset Sequence Segment #2 (P715)
9 Preset Sequence Segment #3 (P720)
P102
Minimum
Frequency
0.0 0.0 {Hz} P103 • P102,P103areactiveforallspeedreferences
• Whenusingananalogspeedreference,also
see P160, P161
p103
Maximum
Frequency
80.0 7.5 {Hz} 500
NOTE
• P103 cannot be set below Minimum Frequency (P102)
• To set P103 above 120 Hz:
- Scroll up to 120 Hz; display shows HiFr (flashing).
- Release p button and wait one second.
- Press p button again to continue increasing P103.
WARNING!
Consult motor/machine manufacturer before operating above rated frequency. Overspeeding the motor/machine
may cause damage to equipment and injury to personnel!
P104
Acceleration
Time 1
30.0 0.0 {s} 3600 • P104 = time of frequency change from 0 Hz
to P167 (base frequency)
• P105 = time of frequency change from
P167 to 0 Hz
• For S-ramp accel/decel, adjust P106
P105
Deceleration
Time 1
30.0 0.0 {s} 3600
EXAMPLE: IF P103 = 120 Hz, P104 = 20.0 s and P167 (base frequency) = 60 Hz; then the rate of frequency change
from 0 Hz to 120 Hz = 40.0 s
P106
S-Ramp
Integration
Time
0.0 0.0 {s} 50.0 • P106 = 0.0: Linear accel/decel ramp
• P106 > 0.0: Adjusts S-ramp curve for
smoother ramp

Related product manuals