Commissioning
4.5.8.5 Register 2100 - Network Control Word
Register 2100 - Network Control Word
Bit Description
0 0 = NOT Run Forward
1 = Run Forward
1 0 = NOT Run Reverse
1 = Run Reverse
2 Fault reset on transition from 0 to 1
3 Reserved
4 Reserved
5 0 = Local Control
1 = Network Control *This Bit MUST be set for the drive to
start/stop from Modbus*
6 0 = Local Speed reference
1 = Network Speed reference *This Bit MUST be set for the
drive to accept speed from Modbus*
7 Reserved
8
9
10
11
Network Speed reference (valid when bit 6 set)
0 – Network
1 – keypad
2 – 0-10VDC
3 – 4-20mA
4 – Preset #1
5 – Preset #2
6 – Preset #3
7 – Preset #4
8 – Preset #5
9 – Preset #6
10 – Preset #7
11 – MOP
12 0 = No Action
1 = Inhibit (Coast to STOP)
13 0 = No Action
1 = Activate Quick STOP
14 0 = No Action
1 = Force Manual Mode (active only in Network Control, in
PID mode will force open loop)
15 0 = DC brake active
1 = DC brake NOT active
Example of usage: To start the drive write into register 2100 value 0x0061. Since Network reference is set as
well (bit6 = 1), writing into reg. 2101 frequency setpoint will take effect as well.