Configuration
7-250

SHB9300CRV EN 2.0
Frequent activation of the monitoring indicates wrong drive selection, i.e. the occuring braking
energy is too high.
Remedy:
l
Use a 934X supply module or
l
(additional)935X brake units
If several controllers are operated at the same time, operation in a DC-bus might be reasonable.
The generated braking energy of the drive could then be used to drive another controller.
The mains connections would then only take up the energy difference.