During operation
6-3
SHB9300CRV EN 2.0
6.2 Information on operation
Please observe the following for controller operation:
Stop!
l
Cyclic connection and disconnection of the supply voltage at L1, L2, L3 or +U
DC
,-U
G
mgiht
overload the internal input current limit:
Allow at least 3 minutes between disconnection and reconnection.
l
During mains switching (L1,L2,L3) it is not important whether further controllers are supplied
via the DC bus.
6.2.1 Switching on the motor side
l
Switching on the motor side of the inverter is permissible for emergency switch-off.
l
Please note:
Switching while a controller is enabled may cause the fault indication 0Cx
(short-circuit/earth fault in operating case x).
For long motor cables and operation of controllers with smaller output power, leakage
currents through interfering cable capacitances may cause the fault indication OCx.
Switching equipment on the motor side must be dimensioned for DC voltages
(V
DC
max = 800 V).