Commissioning
The commissioning described here applies to the wiring example "Local 2-wire control" shown on the
previous page.
Seng parameters
1. Load default sengs: P700.01 = 1
2. Set the following parameters:
Display code Name Seng
P400.02 Start Digital input 1 [11]
P400.04 Error reset Not connected [0]
P400.08 Run forward Digital input 2 [12]
P400.09 Run reverse Digital input 3 [13]
P400.13 Reverse rotang direcon Not connected [0]
P400.18 Setpoint: Preset B0 Not connected [0]
P400.19 Setpoint: Preset B1 Not connected [0]
P210.00 Min. frequency Applicaon-specic
(see the following diagram)
P211.00 Max. frequency
P220.00 Acceleraon 1
P221.00 Deceleraon 1
P430.02 AI1 freq @ min
P430.03 AI1 freq @ max
P430.02
P211.00
P430.03
P430.02
P210.00
P220.00
P221.00
f
t
AI1
Save parameter sengs
P700.03 = 1 or press key on the keypad for longer than 3 s.
Fault reset
A fault can be reset by switching o and on the main power supply or using the keypad keyboard:
1. Press buon .
2. Press buon .