Parameter Value Comment
Name Delivery Seng range
U
min
boost 0.0 % [0.0 ... 100.0] % Eecve only if Energy saving funcon = On:
Boost of the motor voltage in the range of low speeds.
In the case of conveyor applicaons with an inclined proporon, a
turn-back during start-up can be prevented.
Typical values approx. < 5 %.
I
max
in motor mode device-dependent [0.00 ... Imax] A Maximum motor current
MSEMAxx063-42: 5.6 A (recommended 1.4 ... 5.6 A)
MSEMAxx080-32: 13.2 A (recommended 3.3 ... 13.2 A)
With gearbox, the maximum seng range may be limited.
Reducing the I
max
causes a lower maximum torque.
Drives coupled mechanically No No, yes Reducing compensaon processes in case of heavy and long
conveyed loads which occupy several conveying elements at the
same me.
From rmware version 03.00.00.00
Motor overload seng (I
2
x t)
100.00 % [0.00 ... 250.00] % Limit value for motor overload cut-o.
Recommended seng: 100 %
Starng value of motor overload
(I
2
x t)
50.00 % [0.00 ... 100.00] % Recommended seng for operaon according to UL: 50.00 %
Motor brake switching threshold 100/i rpm [0 ... 499.9/i] rpm Motor brake is switched if the value is exceeded or is too low.
Higher value: In the case of conveyor applicaons with an inclined
proporon, a turn-back during start-up can be prevented.
Brake resistor R - ohms [150.0 ... 500.0]
Ohms
Enter data of a connected brake resistor correctly.
If ed in the factory:
If an internal brake resistor is used, the values of the brake
resistor are preset.
If an external brake resistor is used, the values of the brake
resistor are preset. Only the rated power can be increased from
20 W to max. 40 W if the mean speed is > 1000 rpm
(mathemacal mean of the process speeds in relaon to the
motor speed, without standsll).
Rated power of brake resistor - W [10 ... 65535] W
Thermal capacity of brake
resistor
- kWs [0 ... 6553.5] kWs
Reducon of brake chopper
threshold
0 V [0 ... 150] V The threshold is reduced by the voltage value set here.
The switching threshold is adapted to the dierent mains voltage
ranges.
Reducon by 20 ... 30 V can prevent overvoltage for operaon in
generator mode.
Impact of oscillaon damping 5.00 % [0.00 ... 250.00] % For the suppression of no-load oscillaons. Typically, the impact has
to be increased for this purpose.
Oscillaon damping lter me 50 ms [2 ... 250] ms
Before inial switch-on
That the drive does not show any visible signs of damage.
Is the mechanical xing o.k.?
Is the electrical connecon o.k.?
Are all rotang parts and surfaces that may become hot protected against contact?
Is the featherkey radially secured during the test run without output elements?
Have all screwed connecons of the mechanical and electrical parts been ghtened?
Is the free supply and removal of cooling air ensured?
Has the PE conductor been connected correctly?
Have the protecve devices against overheang (e.g. temperature sensor evaluaon) been
acvated?
Is the contact of good electrical conducvity if a PE connecon on the motor housing is
used?
Aer a long period of downme or aer overhauling the motor, check the insulaon
resistance prior to inial switch-on, as condensaon may have formed.
If the values measured are ≤1 kΩ per volt of the rated voltage, the insulaon resistance is
inadequate and no voltage is to be applied.
Dry the winding unl the insulaon resistance is >1 kΩ per volt of the rated voltage.
Commissioning
Before inial switch-on
45