EasyManua.ls Logo

Lenze g500 - Page 112

Lenze g500
132 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Single drive connecon according to EN 60204-1
GND is bridged if the "DI/DO−GND bridged" version is specied on the nameplate.
Fuse data (F1 ... F3)
Motor MSEMA☐☐063-42 MSEMA☐☐080-32
Cable installaon in compli-
ance with
EN 60204-1
Installaon method B2
Fuse
Characteriscs gG/gL
Typ. rated current A 6 10
Max. rated current A 16 16
Semiconductor fuse
Characteriscs gRL
Typ. rated current A 6 10
Max. rated current A 16 16
Circuit breaker
Characteriscs C
Typ. rated current 6 10
Max. rated current A 16 16
Use of copper cables insulated with PVC
Conductor temperature < 70 °C, ambient temperature < 40 °C
No bundling of cables or wires, thee wires under load
Electrical installaon
Mains connecon
Connecon according to EN