EasyManua.ls Logo

Lenze g500 - Page 113

Lenze g500
132 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Connecon for group drive according to EN 60204-1
L1
L2
L3
N
PE
F1 … F3
K
M
3~
+
A
1
I
N1
PE L1 L2 L3
M
3~
+
A
2
I
N2
PE L1 L2 L3
M
3~
+
A
3
I
N3
PE L1 L2 L3
M
3~
+
A
4
I
N4
PE L1 L2 L3
M
3~
+
A
n
I
Nn
PE L1 L2 L3
Max. total rated mains currents at 40 °C
Cable installaon in compli-
ance with
EN 60204-1
Installaon method B2
Cable cross‐secon
mm
2
1.5 2.5
(I
N1
+ I
N2
+ I
N3
+ I
Nn
) x 80% A 7.6 12.2
Fuse
Characteriscs gG/gL
Typ. rated current A --- ---
Max. rated current A 10 16
Circuit breaker
Characteriscs gRL
Typ. rated current A --- ---
Max. rated current A 10 16
4Rated data ^ 71
Use of copper cables insulated with PVC
Conductor temperature ≤70 °C, ambient temperature ≤40 °C
No bundling of cables or wires, thee wires under load
Electrical installaon
Mains connecon
Connecon according to EN
53