Parameter Name / value range / [default seng] Info
14 Digital input 4 State of X3/DI4, taking an inversion set in 0x2632:004 (P411.04) into
consideraon.
15 Digital input 5 State of X3/DI5, taking an inversion set in 0x2632:005 (P411.05) into
consideraon.
50 Running TRUE if inverter and start are enabled and output frequency > 0.2 Hz.
Otherwise FALSE.
51 Ready for operaon TRUE if inverter is ready for operaon (no error acve, no STO acve and
DC-bus voltage ok). Otherwise FALSE.
53 Stop acve TRUE if inverter is enabled and motor is not started and output fre-
quency = 0.
54 Quick stop acve TRUE if quick stop is acve. Otherwise FALSE.
58 Device warning acve TRUE if warning is acve. Otherwise FALSE.
A warning has no impact on the operang status of the inverter.
A warning is reset automacally if the cause has been eliminated.
59 Device fault acve TRUE if a fault is acve. Otherwise FALSE.
In the event of a fault, the motor is brought to a standsll with the
quick stop ramp. The inverter is then disabled.
Excepon: In case of a serious fault, the inverter is disabled immedi-
ately. The motor becomes torqueless (coasts).
The error state will be le automacally if the error condion is not
acve anymore.
The restart behaviour aer trouble can be congured. 4Automac
restart ^ 312
60 Heatsink temperature warning acve TRUE if current heatsink temperature > warning threshold for tempera-
ture monitoring. Otherwise FALSE.
Display of the current heatsink temperature in 0x2D84:001 (P117.01).
Seng of the warning threshold in 0x2D84:002.
69 Rotaonal direcon reversed TRUE if output frequency is negave. Otherwise FALSE.
70 Frequency threshold exceeded TRUE if current output frequency > frequency threshold. Otherwise
FALSE.
Display of the current output frequency in 0x2DDD (P100.00).
Seng Frequency thresholdin 0x4005 (P412.00).
4Frequency threshold for "Frequency threshold exceeded" trigger ^ 407
71 Actual speed = 0
TRUE if current output frequency = 0 Hz (± 0.01 Hz), irrespecve of the
operang mode. Otherwise FALSE.
Display of the current output frequency in 0x2DDD (P100.00).
78 Current limit reached
TRUE if current motor current maximum current. Otherwise FALSE.
Display of the present motor current in 0x2D88 (P104.00).
Seng for the maximum current in 0x6073 (P324.00).
79 Torque limit reached (from version 02.00) TRUE if torque limit has been reached or exceeded. Otherwise FALSE.
Seng "Posive torque limit" in 0x60E0.
Seng "Negave torque limit" in 0x60E1.
81 Error of analog input 1 acve TRUE if the monitoring of the input signal at the analog input 1 has
responded. Otherwise FALSE.
This trigger is set as a funcon of the following sengs:
Monitoring threshold 0x2636:008 (P430.08)
Monitoring condion 0x2636:009 (P430.09)
The seng of the Error response in 0x2636:010 (P430.10) has no eect
on this trigger.
4Analog input 1 ^ 409
82 Error of analog input 2 acve TRUE if the monitoring of the input signal at the analog input 2 has
responded. Otherwise FALSE.
This trigger is set as a funcon of the following sengs:
Monitoring threshold 0x2637:008 (P431.08)
Monitoring condion 0x2637:009 (P431.09)
The seng of the Error response in 0x2637:010 (P431.10) has no eect
on this trigger.
4Analog input 2 ^ 413
Conguring the network
General network sengs
181