Product data sheet
I55BE230F10V1000LS
16238805
©Lenze 07/04/2020 www.lenze.com
Inverter product series
I55BE230F10V1000LS
16238805_datatable.xls
16238805_datatable.csv
16238805_3D.stp
Note:Themodelshownisasimplifiedrepresentation.Minordeviationsmayoccur. 3DHandlingCommands
Rotate Zoom Pan
Technical product information
Inverterproductseries i550Frequencyinverter
Inverter i550-C3/400-3
Type I55BE230F10V1000LS
Ratedpower 3kW/4HP
RatedpowerLD 4kW/5HP
Ratedmainsvoltage 3/PE400/480VAC
Outputcurrent 7.3/6.3A
OutputcurrentLD 8.8/7.6A
RFIfilter Integrated
Outputfrequency 0-599Hz
I/Oextension StandardI/O
Fieldbusnetwork PROFINET
Enclosure IP20
Mountinglocation Controlcabinet
Weight/unit 1.650KG
1/2

Questions and Answers

  • M
    Matthew FreemanSep 9, 2025
    What does a heatsink fan warning mean on Lenze I55BE230F10V1000LS?
    • H
      Hannah AllenSep 9, 2025
      If your Lenze Inverter displays a heatsink fan warning, you should clean the fan and ventilation slots. If required, replace the fan.
  • M
    Mr. Thomas JohnsonAug 23, 2025
    What to do if Lenze Inverter shows device utilization (Ixt) too high?
    • W
      William BaileyAug 23, 2025
      If your Lenze Inverter displays an error indicating the device utilization (Ixt) is too high, consider the following: * Verify the drive sizing is appropriate for the application. * Reduce the maximum overload current of the inverter (parameter 0x6073). * For applications with high mass inertias, reduce the maximum overload current of the inverter (0x6073) to 150%.
  • J
    James JenningsAug 25, 2025
    What to do if Lenze I55BE230F10V1000LS has short circuit or earth leakage on motor side?
    • S
      Sara MunozAug 25, 2025
      If your Lenze Inverter reports a short circuit or earth leakage on the motor side, take these steps: * Inspect the motor cable for damage. * Consider the length of the motor cable. * Use a shorter or lower-capacitance motor cable.
  • K
    Kurt SalasAug 26, 2025
    How to fix Lenze Inverter power section overtemperature?
    • E
      Erin FrancisAug 27, 2025
      If your Lenze Inverter is experiencing a power section overtemperature issue, try the following: * Check the mains voltage. * Ensure the device has sufficient cooling by checking the heatsink temperature (0x2D84:001). * Clean the fan and ventilation slots, and replace the fan if needed. * Reduce the switching frequency (0x2939).
  • L
    leenicholasAug 27, 2025
    What to do if Lenze I55BE230F10V1000LS shows i²*t overload (thermal state)?
    • S
      Samantha TorresAug 27, 2025
      If the Lenze Inverter indicates an i²*t overload (thermal state), you can try the following: * Verify the drive sizing is adequate. * Inspect the machine/driven mechanics for excessive load. * Check the motor data settings. * Reduce the values for slip compensation (0x2B09:001, 0x2B09:002) and oscillation damping (0x2B0A:001, 0x2B0A:002).
  • D
    Dr. James Terry IIAug 29, 2025
    How to resolve DC bus overvoltage on Lenze Inverter?
    • S
      Stephanie MontesAug 29, 2025
      If the Lenze Inverter displays a DC bus overvoltage error, you can: * Reduce the dynamic performance of the load profile. * Check the mains voltage. * Check the settings for the brake energy management.
  • M
    Mrs. Ann MitchellSep 18, 2025
    What to do if automatic start is disabled on Lenze I55BE230F10V1000LS?
    • G
      Grant BaileySep 18, 2025
      If automatic start is disabled on your Lenze Inverter, deactivate the start command and reset the error.
  • P
    Paul DrakeSep 18, 2025
    How to exit keypad full control active on Lenze Inverter?
    • D
      Daniel AllenSep 22, 2025
      If Keypad full control is active on your Lenze Inverter, to exit the control mode, press the keypad key.
  • R
    Robert PalmerSep 7, 2025
    What to do if DC-bus voltage is too low for switch-on in Lenze Inverter?
    • G
      garyfigueroaSep 8, 2025
      If the DC-bus voltage is too low for switch-on in your Lenze Inverter, you should: * Check the mains voltage. * Check the fuses. * Check the mains settings.
  • B
    Bobby AllisonSep 4, 2025
    How to resolve high device utilization (Ixt) in Lenze Inverter?
    • G
      Gregory StephensSep 4, 2025
      If your Lenze Inverter indicates that the device utilisation (Ixt) is too high, you should: * Check drive sizing. * Reduce the inverter's maximum overload current. * In case of high mass inertias, reduce maximum overload current of the inverter to 150 %.

Lenze I55BE230F10V1000LS Specifications

General IconGeneral
BrandLenze
ModelI55BE230F10V1000LS
CategoryInverter
LanguageEnglish