7
Technical data
Operang Instrucons i550-Cabinet
3 Technical data
3.1 Standardsandoperangcondions
Conformities CE 2014/35/EU, 2014/30/EU
EAC TR TC 004/2011, TP TC 020/2011
RoHS 2 2011/65/EU
Approvals CULUS UL 61800-5-1, CSA 22.2 No. 274
Energy efficiency Class IE2 EN 50598-2
Degree of protection IP20 EN 60529 (except in wire range of terminals)
NEMA 250 (type 1 protection against accidental
contact only)
Open type Only in UL-approved systems
Power systems TT, TN Voltage against earth: max. 300 V
IT Apply the measures described for IT systems!
Mains switching 3 x within one minute possible
Operation with residual current circuit
breaker
(optional)
(120-V network and 230-V network)
Up to 4 kW 30 mA, above this 300 mA
Operation with residual current circuit
breaker
(optional)
(400-V network)
Up to 4 kW 30 mA, above this 300 mA
Cable length without EMC category max. 100 m (≤ 5.5 kW max. 50 m)
Cable length for EMC Category C2 max. 20 m (≤0.37 kW max. 15 m)
Category C3 max. 35 m (≤0.37 kW max. 15 m)
Switching frequencies 2, 4, 8, 16 kHz. The rated output currents apply at
45 °C and switching frequencies of 2 and 4 kHz, and
at 40 °C and switching frequencies of 8 and 16 kHz
Ambient temperature 55 °C (derating of 2.5 %/ °C above 45 °C)
Max. output frequency 0 Hz ... 599 Hz
Overload capacity
(120-V network and 230-V network)
200 % for 3 s; 150 % for 60 s
Overload capacity
(400-V network)
200 % for 3 s; Heavy Duty: 150 % for 60 s;
Light Duty: 125 % for 60 s
3.2 ConnecontotheITsystem
NOTE
Electrical voltage
Internal components have earth/ground potenal if the IT screws are not removed.
The monitoring devices of the IT system will be triggered.
Before connecon to an IT system be absolutely sure to remove the IT screws.