16
Electrical installaon
Operang Instrucons i550-Cabinet
5.10 3-phasemainsconnecon480V
Terminaldata,3-phase480V
I55AxxxF I55BxxxF I55AxxxF I55AxxxF I55AxxxF I55AxxxF I55AxxxF I55AxxxF I55AxxxF I55BxxxF I55AxxxF I55AxxxF I55AxxxF
Inverter [kW] 0.37 ... 2.2 3 ... 4 3 ... 5.5 7.5 ... 11 15 ... 22 0.37 ... 5.5 7.5 ... 11 15 ... 22 0.37 ... 2.2 3 ... 4 3 ... 5.5 7.5 ... 11 15 ... 22
Connecon Mains connecon X100 PE connecon Motor connecon X105
Connecon type Pluggable screw terminal Screw terminal PE screw Pluggable screw terminal Screw terminal
Min. cable cross-secon mm² 1 1.5 1
Max. cable cross-secon mm² 2.5 4 6 16 35 6 16 25 2.5 2.5 6 16 35
Stripping length mm 8 8 9 11 18 10 11 16 8 8 9 11 18
Tightening torque Nm 0.5 0.6 0.5 1.2 3.8 2 3.4 4 0.5 0.5 0.5 1.2 3.8
Tools required 0.5 x 3.0 0.5 x 3.0 0.6 x 3.5 0.8 x 4.0 0.8 x 5.5 Torx key 20 PZ2 0.5 x 3.0 0.5 x 3.0 0.6 x 3.5 0.8 x 4.0 0.8 x 5.5
Fusing data/performance data
Inverter [kW] 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 11 15 18.5 22
Rated output current (8 kHz)
(Heavy Duty)
A 1.1 1.6 2.1 3 3.5 4.8 6.3 8.2 11 14 21 27 34 40.4
Max. output current (15 s) A 1.7 2.4 3.2 4.5 5.3 7.2 9.5 12.3 16.5 21 31.5 40.5 51 61
Rated output current
(Light Duty)
A - - - - - - - 7.6 9.8 13.2 18.3 25.2 32.4 40.8
Max. output current (15 s) A - - - - - - - 9.5 12.3 16.5 21 31.5 40.5 51
Operaonwithoutmainschoke
Rated mains current A 1.5 2.1 2.8 3.7 4.5 6.5 8 10.5 14.3 16.6 23.7 32.3 40.3 47.4
Fuse
Characterisc gG/gL or gRL
Max. rated current A 10 10 10 16 16 16 25 25 25 32 32 63 63 63
Circuit breaker
Characterisc B
Max. rated current A 10 10 10 16 16 16 25 25 25 32 32 63 63 63
Operaonwithmainschoke
Rated mains current A 1.2 1.7 2.2 2.5 3.1 4.4 5.8 7.5 10.3 13.1 18.6 24 30 35.3
Fuse
Characterisc gG/gL or gRL
Max. rated current A 10 10 10 16 16 16 25 25 25 32 32 63 63 63
Circuit breaker
Characterisc gG/gL or gRL
Max. rated current A 10 10 10 16 16 16 25 25 25 32 32 63 63 63
Earth-leakage circuit breaker
3-phase mains connecon ≥ 30 mA, type B ≥ 300 mA, type B
In case of Light Duty above 15 kW and Heavy Duty above 30 kW, a mains choke must be used.
Mainsconnecon
+UG
3/PE
AC 340 V ... 528 V
45 Hz ... 65 Hz
F1
F3
Q1
X100
L1
L2
L3
PE
N
L3
L2
3/N/PE
AC 480 V
-UG
Motorconnecon
X105
U
V
W
Rb1
Rb2
M
3~