17
Electrical installaon
Operang Instrucons i550-Cabinet
Terminaldata,3-phase480V
I55AxxxF I55AxxxF I55AxxxF I55AxxxF I55AxxxF I55AxxxF I55AxxxF I55AxxxF
Inverter [kW] 30 ... 45 55 ... 75 90 ... 132 30 ... 75 90 ... 132 30 ... 45 55 ... 75 90 ... 132
Connecon Mains connecon X100 PE connecon Motor connecon X105
Connecon type Screw terminal PE screw PE bolt Screw terminal
Min. cable cross-secon mm² 1 1.5 1
Max. cable cross-secon mm² 50 95 150 25 150 50 95 150
Stripping length mm 19 22 28 16 - 19 22 28
Tightening torque Nm 4 10 18 4 10 4 10 18
Tools required Hexagon socket
5
Hexagon socket
6
Hexagon socket
8
PZ2 Wrench size 13 Hexagon socket
5
Hexagon socket
6
Hexagon socket
8
Fusing data
Inverter [kW] 30 37 45 55 75 90 110 132
Rated output current (8 kHz)
(Heavy Duty)
A 52 65 77 96 124 156 180 -
Max. output current (15 s) A 78 98 116 144 186 234 270 -
Rated output current
(Light Duty)
A 48.5 62.4 78 92.4 115 149 187 216
Max. output current (15 s) A 61 78 98 116 144 186 234 270
Operaonwithmainschoke
Rated mains current A 45.7 57 66.7 83 113 146 168 -
Fuse
Characterisc gG/gL or gRL gR
Max. rated current A 80 100 125 160 160 300 300 300
Circuit breaker
Characterisc B
Max. rated current A 80 100 125 - - - - -
Earth-leakage circuit breaker
3-phase mains connecon ≥ 300 mA, type B
In case of Light Duty above 15 kW and Heavy Duty above 30 kW, a mains choke must be used.
Mainsconnecon
+UG
3/PE
AC 340 V ... 528 V
45 Hz ... 65 Hz
F1
F3
Q1
X100
L1
L2
L3
PE
N
L3
L2
3/N/PE
AC 480 V
-UG
Motorconnecon
X105
U
V
W
Rb1
Rb2
M
3~