Commissioning
Operang Instrucons i550-Cabinet
With the wiring shown below, the inverter can be operated using the control terminals (X3).
• Preset 1 is acvated if DI4 is connected.
• Preset 2 is acvated if DI5 is connected.
• Preset 3 is acvated if DI4 and DI5 are connected at the same me.
GND
AI1
AI2
AO1
10V
24V
DI1
DI2
DI3
DI4
DI5
Setpoint frequency
10 VDC supply
24 VDC, 100 mA supply
Start
Reset error (optional)
Change direction of rotation (optional
Activate preset (Bit 0) (optional)
Activate preset (Bit 1) (optional)
GND
Input range [Hz]:
*P430.02 - *P430.03
7.1.4 Extended terminal control
The following illustraon shows a more extensive wiring of the control terminals (X3) linked
with the respecve parameters.
GND
AI1
AI2
AO1
10V
24V
DI1
DI2
DI3
DI4
DI5
GND
DO1
NO
COM
NC
U/I
*P400.02
Preset 01 (*P450.01)
*P400.04
*P400.13
bit 1 bit 0
0
0
1
1
1
1
Preset 02 (*P450.02)
Preset 03 (*P450.03)
*P400.18
*P400.19
*P420.02
*P420.01
24E
*P201.01
(congured AI1 as
standard setpoint)
Default setting
Start
Reset error
Mark direction of rotation
Activate preset (bit 0)
Activate preset (bit 1)
DO1 activated at
Release brake
Relay activated at
Ready for operation
Analog input 1
24V DC, 100 mA supply, reference for digital inputs
Digital input 1
Digital input 2
Digital input 3
Digital input 4
Digital input 5
Digital output 1
GND for analog and digital signals
Relay NO contact
Relay common contact
Relay NC contact
Preset frequency values
*P430.01 (0 ... 10 VDC signal)
Analog input 2
*
Analog output 1
10V DC supply for potentiometer
P430.02 — *P430.03
range [Hz]:
cong.:
Optional external 24-V-supply
GND for analog and digital signals
7.2 Keypad control
Acvatetemporarykeypadcontrol
1. Press the
key to acvate the keypad control.
2. Press the
key to conrm the keypad control.
Deacvatetemporarykeypadcontrol
1. Press the
key to deacvate the keypad control.
2. Press the
key to conrm the keypad control.
Acvatepermanentkeypadcontrol
If the keypad does not have a
key, the motor control is acvated via the following
parameters:
► Set parameter P200.00 to 1.
► Set parameter P201.01 to 1.
► Set parameter P400.01 to 1.
► Set parameter P400.02 to 1.
Use the
key to start the motor.
Start/control/stop motor with keypad
1. Press the
key to start the motor.
• The keypad shows the motor speed.
2. Use the
key or the key to change the frequency setpoint.
3. Press the
key to stop the motor.
Changerotangdirecon
1. Press the
key.
2. Press the
key to conrm the reversal of rotang direcon.
7.3 Commissioning with the EASY Starter
Commissioning and diagnoscs can be carried out with the EASY starter engineering tool.
A USB module and a standard USB cable (A plug to micro-B plug) is required for this.
hp://www.Lenze.com