EasyManua.ls Logo

Lenze I55BE230F10V1000LS

Lenze I55BE230F10V1000LS
34 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11
Electrical installaon
Operang Instrucons i550-Cabinet
5.6 1-phasemainsconnecon120V
Terminaldata,1-phase120V
I55AxxxA I55AxxxA I55AxxxA I55AxxxA
Inverter [kW] 0.25 ... 0.37 0.75 ... 1.1 0.25 ... 1.1 0.25 ... 1.1
Connecon Mains connecon X100 PE connecon
Motor
connecon X105
Connecon type Pluggable screw terminal PE screw Pluggable screw
terminal
Min. cable cross-secon mm² 1 1.5 1
Max. cable cross-secon mm² 2.5 6 6 2.5
Stripping length mm 8 10 8
Tightening torque Nm 0.5 0.7 2 0.5
Tools required 0.5 x 3.0 0.6 x 3.5 Torx 20 0.5 x 3.0
Fusing data
Inverter [kW] 0.25 0.37 0.75 1.1
Rated output current (8 kHz) A 1.7 2.4 4.2 6
Max. output current (15 s) A 2.6 3.6 6.3 9
Operaonwithoutmainschoke
Rated mains current A 6.8 9.6 16.8 22.9
Fuse
Characterisc gG/gL or gRL
Max. rated current A 16 16 25 25
Circuit breaker
Characterisc B
Max. rated current A 16 16 25 25
Earth-leakage circuit breaker
1-phase mains connecon ≥ 30 mA, type B
Mainsconnecon
1/N/PE
AC 90 V ... 132 V
45 Hz ... 65 Hz
F1
Q1
X100
L1
L2/N
PE
N
L3
L2
3/N/P
AC 208 V ... 240 V
1/N/PE
AC 90 V ... 132 V
45 Hz ... 65 Hz
F1
Q1
X100
L1
L2/N
PE
N
L2
2/N/PE
AC 208 V ... 240 V
Motorconnecon
X105
U
V
W
Rb1
Rb2
M
3~

Related product manuals