30352 0x7690 EPM rmware version incompable Keypad display: EPM-FW incomp.
Cause Error type/response Remedy
The parameter sengs saved in the memory
module are incompable with the rmware ver-
sion.
Fault
•
The data have been loaded into the RAM
memory, but they are incompable.
1.
Execute device command "Load default set-
tings" 0x2022:001 (P700.01).
2.
Execute "Save user data" 0x2022:003
(P700.03) or "Save OEM data" 0x2022:006
(P700.06) device command.
30353 0x7691 EPM data: rmware type incompable Keypad display: EPM: FW incomp.
Cause Error type/response Remedy
The parameter sengs saved in the memory
module are incompable with the rmware
type.
Example: Memory module of an inverter with
an applicaon IO is used in an inverter with a
standard IO.
Fault
•
The data have been loaded into the RAM
memory, but they are incompable.
1.
Execute device command "Load default set-
tings" 0x2022:001 (P700.01).
2.
Execute "Save user data" 0x2022:003
(P700.03) or "Save OEM data" 0x2022:006
(P700.06) device command.
30354 0x7692 EPM data: new rmware type detected Keypad display: UserCU not match
Cause Error type/response Remedy
The parameter sengs saved in the memory
module do not match the inverter hardware.
Fault
•
The data have been loaded into the RAM
memory without being modied, and they
are compable.
•
The sengs loaded must be accepted by the
user (see remedy).
1.
Check parameter sengs.
2.
Reset error.
3.
Execute "Save user data" 0x2022:003
(P700.03) or "Save OEM data" 0x2022:006
(P700.06) device command.
30355 0x7693 EPM data: PU size incompable Keypad display: EPM PU size inco
Cause Error type/response Remedy
The parameter sengs saved in the memory
module are incompable with the inverter.
Fault
•
The data have been loaded into the RAM
memory, but they are incompable.
1.
Execute device command "Load default set-
tings" 0x2022:001 (P700.01).
2.
Execute "Save user data" 0x2022:003
(P700.03) or "Save OEM data" 0x2022:006
(P700.06) device command.
30356 0x7694 EPM data: new PU size detected Keypad display: EPM new PU size
Cause Error type/response Remedy
The parameter sengs saved in the memory
module comply with a dierent hardware.
Example: Memory module of an inverter with a
power of 3 kW is used in an inverter with a
power of 18.5 kW.
Fault
•
The data have been loaded into the RAM
memory without being modied, and they
are compable.
•
The sengs loaded must be accepted by the
user (see remedy).
1.
Check parameter sengs.
2.
Reset error.
3.
Execute "Save user data" 0x2022:003
(P700.03) or "Save OEM data" 0x2022:006
(P700.06) device command.
30357 0x7695 Invalid conguraon of parameter change-over Keypad display: InvalidChgovrCfg
Cause Error type/response Remedy
One or more parameters can no longer be used
for the "Parameter change-over" funcon.
Warning
•
The parameter change-over funcon is deac-
vated.
1.
Check error message for parameter change-
over in 0x4047:001 (P756.01).
2.
Correct the list entry shown in 0x4047:002
(P756.02).