Operating instructions i550 motec frequency inverter | 33
© 03/2022 · EN · www.Lenze.com
Error code Description Classication Remedy Blocking time [s]
6280 Trigger/functions connected incorrectly Trouble
• Check and correct the assignment of the triggers to the functions.
• In network control, the two functions "Inverter enable" (0x2631:001) and "Run" (0x2631:002) can also be set
to "Constant TRUE [1]" to start the motor.
0
7180 Motor overcurrent Error
• Check motor load.
• Check drive sizing.
• Adapt set error threshold (0x2D46:001).
1
FF06 Motor overspeed Error • Adapt the maximum motor speed (0x6080) and the error threshold (0x2D44:001). 1
FF37 Automatic start disabled Error • Deactivate start command and reset error. 0
Error codes