Operating instructions i550 motec frequency inverter | 23
© 03/2022 · EN · www.Lenze.com
Quick commissioning
1. Load default setting: 0x2022:001 = "on / start [1]"
2. Set the following parameters for V/f characteristic control:
0x2540:001: Mains voltage
0x2B01:001: V/f characteristic data: Base voltage
0x2B01:002: V/f characteristic data: Base frequency
0x2915: Minimum frequency
0x2916: Maximum frequency
0x291D:001: Acceleration time 1
0x291D:002: Deceleration time 1
0x2911:001: Setpoint frequency preset 1
0x291D:002
0 Hz
20 Hz
50 Hz
0x2916 =
0x291D:001
0x2915 =
0x2911:001 =
3. Save settings: 0x2022:003 = "on / start [1]"
Start drive:
Drive enabled: X1/SIA = HIGH and X1/SIB = HIGH
Start drive: X3.1/DI1 = HIGH
- The drive rotates with setpoint frequency preset 1 (0x2911:001)
Stop drive again: X3.1/DI1 = LOW
Commissioning
Important notesInitial switch-on
Time
Frequency
Parameter overviewQuick commissioning