Operating instructions i550 motec frequency inverter | 28
© 03/2022 · EN · www.Lenze.com
Index Name Possible settings Selection no. Information
0x291C Quick stop ramp 0.0 ... 1.0 ... 3600.0 s
Quick stop ramp for “MS: Velocity mode”
If the "Quick stop" function is activated, the motor is brought to a standstill within the
deceleration time set here.
The set braking deceleration time refers to the braking delay starting from the set maximum
frequency (0x2916) to standstill. In the case of a lower actual frequency, the actual
deceleration time is reduced accordingly.
Setting is not eective in the operating mode 0x6060 = “CiA: Velocity mode [2]”.