Operating instructions i550 motec frequency inverter | 30
© 03/2022 · EN · www.Lenze.com
Index Name Possible settings Selection no. Information
0x2022:001 Device commands: Load default settings
On / start [1]
1 = reset all parameters in the RAM memory of the inverter to the default setting stored in the
inverter rmware.
All parameter changes made by the user are lost during this process!
This process may take some seconds. When the device command has been executed
successfully, the value 0 is shown.
Loading parameters has a direct eect on cyclic communication: The data exchange for
control is interrupted and a communication error is generated.
O/ready [0] Only status feedback
0x2022:002 Device commands: Save user data
On / start [1]
1 = save current parameter settings in the inverter with mains failure protection.
This process may take some seconds. When the device command has been executed
successfully, the value 0 is shown.
Do not switch o the supply voltage during the saving process!
O/ready [0] Only status feedback