Display code Short designaon Default seng Seng range Address Category
P324.00 Max current 200.0 % 0.0 ... 3000.0 % 0x6073 general
P325.00 Motor torque 1.650 Nm * 0.001 ... 4294967.295 Nm 0x6076 MCTRL
P326.00 Max torque 250.0 % 0.0 ... 3000.0 % 0x6072 general
P327.xx Axis commands
└ P327.04 Idenfy mot. 0 0 ... 1 0x2822:004 general
└ P327.05 Calibrate mot. 0 0 ... 1 0x2822:005 general
P329.xx MaxTrq.Monitor
└ P329.01 Response No response [0] Selecon list 0x2D67:001 MCTRL
└ P329.02 Triggering delay 0.000 s 0.000 ... 10.000 s 0x2D67:002 MCTRL
P330.xx VFC-ECO
└ P330.01 Min. voltage 20 % 20 ... 100 % 0x2B0D:001 MCTRL
└ P330.06 Cos Phi actual - - (Read only) 0x2B0D:006 general
P332.xx Speed controller
└ P332.01 Gain 0.00193 Nm/rpm * 0.00000 ...
20000.00000 Nm/rpm
0x2900:001 MCTRL
└ P332.02 Reset me 80.0 ms * 1.0 ... 6000.0 ms 0x2900:002 MCTRL
P333.xx V/f Imax contr.
└ P333.01 Gain 0.284 Hz/A * 0.000 ... 1000.000 Hz/A 0x2B08:001 MCTRL
└ P333.02 Reset me 2.3 ms * 1.0 ... 2000.0 ms 0x2B08:002 MCTRL
P334.xx Current contr.
└ P334.01 Gain 42.55 V/A * 0.00 ... 750.00 V/A 0x2942:001 MCTRL
└ P334.02 Reset me 4.50 ms * 0.01 ... 2000.00 ms 0x2942:002 MCTRL
P335.xx Moment of inert.
└ P335.01 Motor inera 3.70 kg cm² * 0.00 ... 20000000.00 kg cm² 0x2910:001 MCTRL
└ P335.02 Load inera 3.70 kg cm² * 0.00 ... 20000000.00 kg cm² 0x2910:002 MCTRL
└ P336.02 Ramp me 1.0 s 0.0 ... 60.0 s 0x2948:002 general
P337.xx
└ P337.01 Pos. torqlim src Max torque [0] Selecon list 0x2949:001 general
└ P337.02 Neg. torqlim src (-) Max torque [0] Selecon list 0x2949:002 general
└ P337.03 Act postorqlim x.x % - (Read only) 0x2949:003 general
└ P337.04 Act negtorqlim x.x % - (Read only) 0x2949:004 general
P340.xx Speed limitaon
└ P340.01 Upper limit 0 vel. unit -480000 ... 480000 vel. unit 0x2946:001 general
└ P340.02 Lower limit 0 vel. unit -480000 ... 480000 vel. unit 0x2946:002 general
└ P340.03 Uppspeed lim src Max. frequency [0] Selecon list 0x2946:003 general
└ P340.04 Lowspeed lim src (-) Max. freq. [0] Selecon list 0x2946:004 general
└ P340.05 Upper freq.limit Device for 50-Hz mains:
50.0 Hz
Device for 60-Hz mains:
60.0 Hz
-1000.0 ... 1000.0 Hz 0x2946:005 general
└ P340.06 Lower freq.limit Device for 50-Hz mains:
-50.0 Hz
Device for 60-Hz mains:
-60.0 Hz
-1000.0 ... 1000.0 Hz 0x2946:006 general
└ P340.07 Act uppspeed lim x.x Hz - (Read only) 0x2946:007 general
└ P340.08 Act lowspeed lim x.x Hz - (Read only) 0x2946:008 general
P341.xx Encoder sengs
└ P341.01 Enc. Inc/Rev 128 1 ... 16384 0x2C42:001 general
P342.00 Enc.error resp. Warning [1] Selecon list 0x2C45 general
P350.xx Overspeed monit.
└ P350.01 Threshold 8000 rpm 50 ... 50000 rpm 0x2D44:001 general
└ P350.02 Response Fault [3] Selecon list 0x2D44:002 general
P351.xx ASM motor par.
└ P351.01 Rotor resistance 8.8944 Ω * 0.0000 ... 200.0000 Ω 0x2C02:001 MCTRL
└ P351.02 Mutual induct. 381.9 mH * 0.0 ... 50000.0 mH 0x2C02:002 MCTRL
* Default seng depending on the size. Firmware version 05.00.00.00
Commissioning
Keypad parameter list
90